background image

4098-9839 Smoke Detector Data Reader

Quick Reference Guide

574-498

Rev. A

 1998 Simplex Time Recorder Co.  Gardner, MA 01441-0001 USA

 1998 Simplex International Time Equipment Co., Ltd.  Mississaugua, Ontario L4V 1H3 Canada.

All specifications and other information shown were current as of publication, and are subject to change without notice.

3 5 0 E 4 C 3 D 4 O F 8 E 1 O E

1 B       2 0 % A L M       # 0 0 1

Red

LED

Green

LED

MODE

Reader is in scan mode.

Valid reading with a NORMAL condition.

Valid reading with a TROUBLE condition.

 indicates illuminated LED       

 indicates LEDs that are OFF

NOTES:

1. 

DO NOT depress all push buttons on
the data reader simultaneously, this
can clear the memory.

2. 

The detector must be cleaned or
replaced if the display indicates a
greater than “50%ALM” reading.

3. 

Replace battery when

∗∗∗

 LOW BAT 

∗∗∗

” is displayed.

4. 

Compatible Smoke Detectors:

 

4098-9601, -9602, -9605.

5. 

For future use, not applicable with
basic operation.

Figure 1.  4098-9839 Data Reader

OPERATING INSTRUCTIONS:

To operate the data reader, follow Steps 1 through 6.

1. 

Turn the ON/OFF switch of the reader to the ON position.  The Red LED on
the reader illuminates.

2. 

Point the focusing lens of the reader directly at a compatible smoke detector’s
LED, no more than 12 inches away.  (See Note 4.)

3. 

When a valid reading is made, the Green LED on the reader illuminates.

4. 

After a valid reading is taken there are two possible conditions.  If the
condition is NORMAL the Green LED is lit alone.  If there is a TROUBLE
condition, both the Green and Red LEDs of the reader are illuminated.
(Refer to Figure 1.)

5. 

When both LEDs are illuminated or if greater than “50%ALM” is indicated,
clean or replace the detector.  Refer to Application Manual 574-709 for
detector cleaning.

6. 

Press the SCAN button on the reader to go to the next detector.

Note: The STORE button is not applicable with basic operation.  If accidentally

pressed, take the following steps to clear the reader’s memory.

1. Power the reader OFF.
2. Hold down the STORE and D/L buttons simultaneously.

3. Power the reader ON with the STORE and D/L buttons pressed for five

seconds.

4. Release the buttons.

Figure 2.  Reader Display Information

Focusing Lens:
Aim at a target
(maximum of 12
inches away)

Serial Data Port:
See Note 5

Green LED

Store Button:
See Note 5

D/L (Download) Button:
See Note 5

LCD Display

(Diagnostic data,

See Note 5)

See Note 2

Red LED

ON/OFF Switch:

Powers the reader

ON or OFF

Scan Button:

Press button to put

reader into a scan

mode (indicated by an

illuminated Red LED)

9V Battery Housing:

Located on the back of

the reader

See Note 5

See Note 5

firealarmresources.com