background image

574-763

Rev. A

Install the 4009-9812 Class A Adapter Option Card piggy-backed onto the
Addressable Controller.  Use the following steps and Figure 3 to mount the card.

1.

 

Disconnect the battery and then AC power from the Addressable Controller.

2.

 

Place one of the supplied insulating washers over the threaded end of each
of the three metal standoffs. Screw the three standoffs (Part No. 524-289)
into the threaded holes on the Addressable Controller system board.

3.

 

Plug the two 6-pin headers (on the opposite side of P1 and P2 on the Class
A Adapter Option Card) into connectors P2 and P3 on the Addressable
Controller system board (see Figure 3). Check to verify the proper
alignment of P2 and P3.

4.

 

Install screws (Part No. 440-008) to connect the Class A Adapter Option
Card to the three standoffs (see Figure 3). When you are done, reconnect
AC and battery power.

IDNet INPUT

RUI INPUT

SW1

SW2

SW3

SW4

SW5

PB

4009 TRUEALERT

MAIN BOARD

565-990

LED LED LED

SHLD

RUI

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

LED LED

CH1

E

D C B

A

CH2

CH3

LED

HARDWARE

CONFIG

ADDRESS

SOFTWARE

LED

LED

SHLD

IDNet

Trouble Code LEDs

NAC CHANNEL

INDICATOR LEDs

Figure 3. Class A Adapter Option Card Mounting