574-763
Rev. A
Install the 4009-9812 Class A Adapter Option Card piggy-backed onto the
Addressable Controller. Use the following steps and Figure 3 to mount the card.
1.
Disconnect the battery and then AC power from the Addressable Controller.
2.
Place one of the supplied insulating washers over the threaded end of each
of the three metal standoffs. Screw the three standoffs (Part No. 524-289)
into the threaded holes on the Addressable Controller system board.
3.
Plug the two 6-pin headers (on the opposite side of P1 and P2 on the Class
A Adapter Option Card) into connectors P2 and P3 on the Addressable
Controller system board (see Figure 3). Check to verify the proper
alignment of P2 and P3.
4.
Install screws (Part No. 440-008) to connect the Class A Adapter Option
Card to the three standoffs (see Figure 3). When you are done, reconnect
AC and battery power.
IDNet INPUT
RUI INPUT
SW1
SW2
SW3
SW4
SW5
PB
4009 TRUEALERT
MAIN BOARD
565-990
LED LED LED
SHLD
RUI
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
LED LED
CH1
E
D C B
A
CH2
CH3
LED
HARDWARE
CONFIG
ADDRESS
SOFTWARE
LED
LED
SHLD
IDNet
Trouble Code LEDs
NAC CHANNEL
INDICATOR LEDs
Figure 3. Class A Adapter Option Card Mounting
Mounting
Overview
HOLES FOR
524-289 STANDOFFS
P2, P3 6-PIN
CONNECTORS
firealarmresources.com