8-5
4007ES Panel Programmer Manual (
579-1167)
Viewing, Adding, and Editing Lists,
Continued
Latching Supv
Verification
The ES Panel's Latching Supv Verification (LVS DUCT and LVSUPV) feature activates a
supervisory condition when a device crosses the threshold. This means that the supervisory
condition on the panel does not clear until the point restores to normal and a system reset is
performed.
The ES Panel FACP supports both Domestic (United States) and Canadian versions of
supervisory verification. Refer to “Selecting Canadian or Domestic (US) Operation” for
information on enabling the Canadian or domestic version of alarm verification.
Moving Points between Groups
By default, initiating devices with a latching verification point type are initially put in Supv
Verification Group 0.
To put points into other Supv Verification groups:
1. Open the List Window by selecting the List Tab at the top of the Programmer.
2. Click on the Latching Supv Verification tab at the bottom of the List Window.
3. Click on the Supv Verification group into which you want to move points. Right click and
select Tag List.
4. Use the mouse or arrow keys to highlight each point you want to move into the group. A
point is selected when a “>>” appears to the left of the point. Repeat this step to select other
points.
Selecting Canadian or Domestic (US) Operation
Canadian alarm verification works somewhat differently from the domestic (US) version.
Table 8-1 shows Canadian and domestic (US) operation for the alarm verification feature.
To select Canadian or Domestic (US) operation (Figure 8-3), follow these steps:
1. Right click on one of the groups and select
Properties. The Alarm Verification Properties
dialog appears.
2. Click on the Alarm Verification tab.
3. Click on the drop-down list box and select
Canadian or Domestic operation.
Note:
You only need to set the Verification Timer field
for one of the alarm verification groups. The
programmer sets this field to the same value for
all other groups.
Figure 8-3. Alarm Verification Properties Dialog
Table 8-1. Canadian/Domestic Operation
Type
Operation
Canadian
Operation
Retard Stage
. If a point specified within one of the alarm verification lists
enters an alarm state, the system delays the annunciation of the alarm for 15
seconds
Reset Stage
. When the 15 second timer expires, the system attempts to reset
the initiating device for five seconds.
Confirmation Stage
. After the five second timer expires, the system
evaluates the state of the initiating device for 10 additional seconds. After 10
seconds, if the device is still in alarm, the system immediately annunciates the
alarm.
Domestic
(US)
Operation
Retard Stage
. If a point specified within one of the alarm verification lists
enters an alarm state, the system delays the annunciation of the alarm for 30
seconds
Reset Stage
. When the timer expires, the system attempts to reset the
initiating device for five seconds.
Confirmation Stage
. After the timer expires, the system evaluates the state
of the initiating device for up to 120 additional seconds. After this duration, if
the device is still in alarm, the system immediately annunciates the alarm.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......