9-35
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Scheduling
Options for
Self-Test Wizard
Select the following options in the
Self-Test Wizard
to set up one or more schedules to run the
scheduled self-tests:
• Frequency
• Day
• Time
• Triggering pseudo point
Note:
An automatic self-test can be launched from the TSW instead of the FACP. The pseudo point is a
trigger to execute the scheduled self-test. The triggering point is optional. The purpose is to select a
digital pseudo point to launch a scheduled self-test by overriding the usual date and time condition.
For example, a public TSW digital point can be added to the job as external point and used to trigger
a self-test. The user can run an automatic self-test at any time and on multiple panels at the same
time.
Important: The system pseudo point P503 RUN SCHEDULED SELF-TEST cannot be used
as a triggering point. Doing so will lead to unpredictable behavior.
After configuring the date and time select the following options:
• List of SIGs
• Volume
• Trouble on fault
Step 1. Creating a
New Self-Test
1. Click on the
Custom Control
tab.
2. Click on the
Scheduled Self-Test Wizard
subtab, right click inside the blank area of the
Scheduled Tests
and select the
Create Self-Test
option. A screen similar to the one shown
3. Complete the
Self-Test Name
and
Comments
fields
4. Click
Next
.
Figure 9-40. Wizard entry screen
Continued on next page
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......