Table 9-5 describes actions and their corresponding responses.
Use Case #4: Immediate Release
This use case is the simplest case. No abort switch, no release timers and no cross zone
verification.
Specific Configuration
IDNET points
• Manual release point: MBZAM with SSDUMP point type at address M1-11-0.
• Automatic Release Points: One Smoke detector devices with SUPDET point types at
address at M1-18-0.
• SRP: One SRP (RELEASE) with point type SUPRELS at address M1-36-0.
True Alert Zone
• SIG913 is configured as RELSIG (Releasing horn circuit) and has at least one audible
device from the IDNAC channel.
• SIG915 is configured as RELVIS (Releasing Visual Signal) and has at least one visual
device from the IDNAC channel.
AuxNAC
• SIG3 set as SUPRELS point type.
Create a Hazard Area in Custom Control, Suppression Release Wizard,
• Create Hazard Area window.
1. Hazard Area Name: Area 1
2. Comments: n/a
Continued on next page
Table 9-5. IRI Abort, Actions and Releases
Action
Response
First detector is
triggered.
RELSIG turns on low cadence (Temporal). RELWVIS turns on.
Abort switch is
pressed and held.
No change.
Second detector is
triggered while abort
switch is still pressed.
Keep the abort switch
pressed for more than
one minute.
• RELSIG goes on high cadence (March120). RELWVIS stays on.
• SRP output does not turn on including after Automatic Release Timer expires.
Abort switch is
released
After 10 seconds or the remaining value of the release timer, whichever is greater,
RELSIG goes on steady. RELWVIS stays on. RELVIS goes on. SUPRELS NAC
goes on steady and SRP output goes on steady.
Notes:
• If a second alarm condition occurs while the Abort switch is still pressed, the
automatic release timer resets to the value that has been configured for it. It
begins to count down and will stop at 10 seconds. When the abort switch is
released, the panel starts the release timer countdown at the value of the
countdown timer or at 10 seconds, whichever is greater.
• Pressing the abort switch again and releasing it, when a second alarm is
triggered, has no effect.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......