Field Applications  

The ESB303 limiter allows connecting much more capacitive loads (e.g. LED-power supply / LED-driver) to a pre-installed 
circuit breaker CB. The ESB avoids that the MCB will be tripped. This occurs independent to the objective initial current. 
The result is that the number of A.C. branch lines and the pre-installed MCB can be reduced dramatically. Installation 
cost exhibit a sustained decline. Alternatively, the cross section of the branch lines can be reduced when using smaller 
and faster responding circuit breakers. The cost saving from copper is essential. Sensitive AC networks can be fused 
safer (e.g. Traffic Control Systems, Street-Lighting, Parking Lots and Tunnels). When the ESB303 is installed correctly, 
the neutral wire (N) is looped trough. The inrush protection circuit always acts to the line conductor. The load relates 
to the AC in such a way that a circuit breaker or an earth-leakage-trip works within the limits of the legal rules. This fact 
is also applied while the limiting circuit acts. The ESB303 is designed for capacitive loads, only. The ESB303 cannot be 
used together with transformers, coils, AC-motors & drives, heaters or with DC-voltage at all. 

 

General type information ESB303.LED 

The  ESB303-model  is  a  universal  inrush  current  limiter.  The  concept  design  is  made  to  construct  optimized  A.C. 
networks  in  the  building  automation,  the  machine  building  and  in  the  lighting  sector.  Tripping  the  installed  circuit 
breaker will be effectively prevented. The inrush limiting time is adjusted to the values of a typical LED switch mode 
power supply or a LED-driver. The connectable load capacity is such as high, that even in the extremes cases it is rather 
impossible to exceed it in a 16A network. Installed contractors will be discharged and their lifetimes will considerable 
increase. Note that the ESB303 is not designed to operate together with gas induction lamps or other conventional 
lighting device. The ESB303 is designed for capacitive loads, only. 

 

              

 

Design-In of the ESB303 into A/C networks  

The  ESB303  model  is  a  precise  inrush  current  limiter  with  an  overall  tolerance  of  ±6%  of  the  face  value.  For  the 
dimension  of  an  upstream  connected circuit  breaker  the  R.M.S  is  the  key  value  of  the  inrush  current,  not  the  peak 
current. The thermal trigger point will not be met, even while using an extreme fast CB. All-dominant is the magnetic 
trigger current. By using the empirical formula I

(peak)

 x 0,707

(factor) 

= I

(r.m.s.)

 the tripping current can be defined exact. Bear 

in mind that all the higher the inrush current is, all the faster the input capacitor of several connected switch mode 
power supplies will be loaded. Deduced by this fact we can say that within a 230V or a 400V 16A A/C N-wire network 
the ESB303.LED.200/400V limiter is the right selection for a B13A 10kA or a B16A MCB 10kA. The technical table on 
page 2 shows the R.M.S value of the ESB303. Do not use an MCB that has a larger value than 16A 

 

 

 

 

 

 

 

 

 

(Fig.5 limiting time T

on

)             

           (Fig.7 inrush without ESB303) 

 

 

 

 

 

 

 

 

 
(Fig.6 AC dump detection T

off

           (Fig.8 inrush with ESB303)

 

 

t

on

 

Fig.7 and Fig.8 
Fig.7 and Fig.8 show the typical start 
behavior  of  a  NTC  protected  switch 
mode  power  supply.  The  used  test 
item  is  a  CAMTEC  HSE10001.24T 
power  supply  with  an  output  of 
24V/42A (1008W) on DIN-Rail. 
The peak current recordings show the 
precise  limiting  of  the  inrush  from 
formerly  62A

peak

  to  16A

peak

.  The 

corresponding  R.M.S  level,  that  is 
responsible for the magnetic tripping 
of  the  MCB,  is  mark  down  by  factor 
0,707. After the time T

on

 elapsed it is 

identified  that  the  power  supply 
starts  neatly  into  the  continuous 
operation  mode.  Now  the  current  is 
absorbed pulse-shaped from the AC.  
In  detail  the  full  load  R.M.S.  current 
consumption  level  of  the  HSE10001 
hits 9A @ 230Vac.  

62A

peak

 

16A

peak

 

230Vac 

230Vac 