6.2.
CONTROL OF THE RELAY OUTPUTS
The control of the object (measured signal) is realized via relay outputs.
If device is not equipped with one or more relay outputs, menus referring to this
relays are not available.
Modes of the control can be changed depend on the values of parameters
“SEtP”
,
“SEt2”, “HYSt”
,
“modE”
,
“t on”
,
“toFF”
,
“unit”
and
“AL”.
Depend on
“modE”
parameter,
relays can be not used or controlled over one or two thresholds values.
If one threshold is used (
) the relay can be turned on (
“modE”
=
”on”
) or off
(
“modE”
=
”oFF”
) when the input signal value is contained in
zone A.
If two thresholds are
used (
) the relay will be turned on when value of input signal is contained in
zone A
(
“modE”
=
”in”
) or
zone B
(
“modE”
=
”out”
) and turned off if the signal is contained in the
second one.
Figure 6.5. One threshold control of the relay outputs
Figure 6.6. Two threshold control of the relay outputs
The relay outputs and LEDs (named
R
) can be controlled depend on both - the
current value and the peak value (when peak detection is active) of the input signal.
22
i
i
zone A
zone B
measure
”SEtP” parameter
”HYSt” parameter
state of
relay
zone B
zone A
zone B
measure
”SEtP” or ”SEt2” parameter
”HYSt” parameter
state of
relay