User manual - METER SUR-94
Register
Write
Range
Register description
56h
Yes
0 ÷ 1
“
H r3
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
57h
Yes
0 ÷ 1
“
H r4
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
58h
Yes
0 ÷ 1
“
HOUt
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
70h
5
Yes
-999 ÷ 1999
The value of „
X
” coordinate of point
no. 1
of the user defined
characteristic, expressed in 0.1%
71h
5
Yes
-999 ÷ 9999
The value of „
Y
” coordinate of point
no. 1
of the user defined
characteristic, no decimal point included
72h
5
÷ 95h
5
Further pairs of „
X
” - „
Y
” coordinates of points
no. 2
÷
19
of the
user defined characteristic
96h
5
Yes
-999 ÷ 1999
The value of „
X
” coordinate of point
no. 20
of the user defined
characteristic, expressed in 0.1%
97h
5
Yes
-999 ÷ 9999
The value of „
Y
” coordinate of point
no. 20
of the user defined
characteristic, no decimal point included
A0h
1
Yes
0 ÷ 3
“
Omod
” parameter in “
OUtP
” menu (active current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20mA
mode;
2
-
current output enabled with
0÷20mA
mode
;
3
-
current output controlled via RS-485 interface
Yes
0 ÷ 2
“
Omod
” parameter in “
OUtP
” menu (passive current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20mA
mode;
2
-
current output controlled via RS-485 interface
Yes
0 ÷ 5
“
Omod
” parameter in “
OUtP
” menu (active voltege output mode)
0
- voltage
output disabled
;
1
- voltage
output enabled
with
0
÷5V
mode;
2
- voltage
output enabled with
1÷5V
mode
;
3
- voltage
output enabled with
0÷10V
mode
;
4
- voltage
output enabled with
2÷10V
mode
;
5
- voltage
output controlled via RS-485 interface
A1h
1
Yes
-999 ÷ 9999 “
OUtL
” parameter in “
OUtP
” menu,
no decimal point included
A2h
1
Yes
-999 ÷ 9999 “
OUtH
” parameter in “
OUtP
” menu,
no decimal point included
A3h
1
Yes
0 ÷ 999
“
Lo r
” parameter in “
OUtP
” menu, for active current output and
active voltage output, expressed in 0.1%
Yes
0 ÷ 299
“
Lo r
” parameter in “
OUtP
” menu for passive current output,
expressed in 0.1%
A4h
1
Yes
0 ÷ 199
“
Hi r
” parameter in “
OUtP
” menu for active and passive current
output, expressed in 0.1%
Yes
0 ÷ 99
“
Hi r
” parameter in “
OUtP
” menu for active voltage output,
expressed in 0.1%
A5h
1
Yes
0 ÷ 3
“
AL
” parameter in “
OUtP
” menu (active current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA;
3
- 0 mA
Yes
0 ÷ 2
“
AL
” parameter in “
OUtP
” menu (passive current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA
50