User manual for regulated current source SZP-73
- Do not use the unit in areas with significant temperature variations, exposed to
condensation or icing.
- Do not use the unit in areas exposed to direct sunlight.
- Make sure that the ambient temperature (e.g. inside the control box) does not
exceed the recommended values. In such cases forced cooling of the unit must
be considered (e.g. by using a ventilator).
The unit is designed for operation in an industrial environment and must
not be used in a household environment or similar.
2.
GENERAL CHARACTERISTICS
Regulated current source
SZP-73
allows generation of user settable current (in range
4-20 mA). Increasing and decreasing of output current can be made using local keyboard.
Device displays present value of output current recalculated according to set display range
(-999 do 9999 with free selectable decimal point). Quick view and regulation of output current
is possible at any time. The device can replace all two wire analogue current sources
(4-20mA) used for controlling of industrial processes.
3.
TECHNICAL DATA
Power supply voltage
(depending on version)
External fuse (required)
Power consumption
85...
230
...260V AC/DC; 50 ÷ 60 Hz
or 19...
24
...50V DC; 16...
24
...35V AC
T - type, max. 2 A
max. 4.5 VA @ 85 ÷ 260V AC/DC
max. 4.5 VA @ 16V ÷ 35V AC
max. 4.5 W @ 19V ÷ 50V DC
Outputs
current:
sensor power supply:
4÷20 mA (passive), isolated from other terminals
24V +5%, -10% / max. 100 mA, stabilized
Current output ext. supply voltage.
min. 6.5 V
Precision
±20
µ
A
Stability
typ. 50 ppm / °C
Display range
-999 ÷ 9999, plus decimal point
Communication interface
RS 485, 8N1 and 8N2, Modbus RTU,
not separated
Baud rate
1200 bit/s ÷ 115200 bit/s
Display
(depending on version)
LED, 4 digit, 13mm height, two-colour (red and green)
or (for IP 65 version) 5 digit, 9mm height, red
Data memory
non-volatile memory, EEPROM type
Protection level
IP 65 (from front, after using waterproof cover)
IP 40 (from front)
IP 20 (housing and connection clips)