background image

User manual - GALVANIC SEPARATOR SGS-61 

3. 

       TECHNICAL DATA

 

 

Input loop

Current

4 ÷ 20 mA; I

IN

  

MIN

 =  3,9 mA; I

IN

  

MAX

 = 24 mA

Voltage drop

max. 5,5V

Supply type

from current loop

Output loop

Current

 4 ÷ 20 mA; I

OUT 

 

MIN

 =  3,9 mA;  I

OUT

  

MAX 

= 24 mA

Current loop supply

9 ÷ 30 V DC 

(any polarisation on OUT1, OUT2)

Max load resistance

max. 1kΩ  (for supply: 30V / I

OUT

 = 20 mA), 

[R

O. MAX

 = (U

supply

 – 9V) / I

OUT

]

Other

Transmittance factor

K

 =  I

OUT

 / I

IN

   = 1

Separation

galvanic separation between input and output loop

Insulation voltage

750V

Temperature stability

0,05 % / °C 

Bandwith (3dB)

200 Hz

Protection level

IP 20

Housing type

Housing dimensions

DIN rail mounted (35 mm rail)

80 x 6,1 x 93,8 mm

Weight

35 g

Operating temperature
(depending on version)

0°C to +50°C
or -20°C to +50°C

Storage temperature
(depending on version)

-10°C to +70°C
or -20°C to +70°C

Screws tightening max. torque

0,5 Nm

Max. connection leads diameter

2,0 mm

2

EMC

according to: PN-EN 61326-1

Isolation between primary and secondary circuit is only functional isolation and can't be 

use as protection against electric shock.

This   is   a   class   A  unit.   In   housing   or   a   similar   area   it   can   cause   radio  
frequency  interference.   In such  cases  the user  can  be requested  to  use  
appropriate preventive measures. 

4

Summary of Contents for SGC-61

Page 1: ...l GALVANIC SEPARATOR SGS 61 Input type 4 20 mA Supply from current loop Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes wi...

Page 2: ...SIGNAL ADJUSTMENT 11 Explanation of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operation of the device Not complying with the guidel...

Page 3: ...tage and interference filters Do not attempt to disassemble repair or modify the unit yourself The unit has no user serviceable parts Defective units must be disconnected and submitted for repairs at...

Page 4: ...bility 0 05 C Bandwith 3dB 200 Hz Protection level IP 20 Housing type Housing dimensions DIN rail mounted 35 mm rail 80 x 6 1 x 93 8 mm Weight 35 g Operating temperature depending on version 0 C to 50...

Page 5: ...on should be conducted by qualified personnel Read the basic safety requirements on page 3 prior to starting the installation All installation works must be conducted with a disconnected power supply...

Page 6: ...EMBLY Disconnect the power supply prior to starting assembly Check the correctness of the performed connections prior to switching the unit on Figure 4 1 Housing dimensions Figure 4 2 Method of mounti...

Page 7: ...stallation according to this manual local safety and EMC regulations Wiring must meet appropriate standards and local regulations and laws Tighten the clamping screws The recommended tightening torque...

Page 8: ...netically induced interference the use of twisted couples of signal cables so called spirals is recommended The spiral best if shielded must be used with RS 485 serial transmission connections Figure...

Page 9: ...mple of device connection Signal polarization on input connectors IN IN is fixed Signal polarization on output connectors OUT1 OUT2 is free 9 4 5 1 power supply 24V two wire transducer R0 power supply...

Page 10: ...es not have any internal replaceable components available to the user Pay attention to the ambient temperature in the room where the unit is operating Excessively high temperatures cause faster ageing...

Page 11: ...ment output current are available Figure 5 1 Potentiometers location Potentiometers description P1 output current adjustment at IIN 4 00 mA P2 output current adjustment at IIN 20 00 mA After regulatio...

Page 12: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: