User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Fig. 7.98.Schematic diagram for the RTD input and Relay output modules
To control temperature in the object shown in
, it is necessary to configure one
Logical channel
and
Relay output
.
For reading PT100 sensor temperature:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
Logical channel
such as
1
,
–
in the
Name
parameter write
Feedback
,
–
Mode
parameter set as
Hardware input
,
–
Source
parameter set as
Inp.A1 : RTD
–
enter the
Configure source
submenu:
•
Mode
parameter set as
Pt100
,
•
in
Low limit
parameter write
-100°C
,
•
in
High limit
parameter write
600°C,
–
for
Displaying
parameter block:
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0.0
,
•
in
Graph low
parameter write
0°C
,
•
in
Graph high
parameter write
100°C
,
For Relay output configuration:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Built-in outputs
menu,
–
using the arrows in the top navigation bar, select a relay output which is connected
174
R
45
4
re
la
y
o
u
tp
u
ts
5
A
/2
50
V
n01
n02
n03
n04
n05
n06
n07
n08
n09
n10
n11
n12
O
U
T
1
O
U
T
2
O
U
T
3
O
U
T
4
PT100
sensor
Slot A
Inp.A1 : RTD
Inp.A2 : RTD
Inp.A3 : RTD
Inp.A4 : RTD
RT4
4 RTD inputs
I
N
1
I
N
2
I
N
3
I
N
4
n01
n02
n03
n04
n05
n06
n07
n08
n09
n10
n12
n13
n14
n15
n16
n11
Heater
Power supply
L
N
Slot C
O
u
t.
C
1
:
R
e
la
y
Controlled object
Power supply
(depending on version)
1
2
8
5
6
7
3
4
+24V DC ±5%
(
I
max. = 200mA)
digital input
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
SERVICE