User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
7.8.11.7. Application in Math function mode
See also:
Chapter 7.8.6. Logical Channels - Math function mode
Task:
The task is to create a logical channel with the function returns the value of a logical
channel (
X [i]
) selected by the other logical channel (
Y
).
Suppose we have defined four logical channels 1, 5, 8, 12 in the
Set point
mode.
However, in the logical channel 2 there will be the value derived from the temperature sensor.
In the logical channel 3 create the math function
X [i] selected by the Y
. Using the value of
channel 2 we select the value from channels 1, 5, 8, 12.
The result of this function is placed in
Y value Value of logical channel 3
Y≤0
Value of logical channel 1
0<Y≤1
Value of logical channel 5
1<Y≤2
Value of logical channel 8
Y>2
Value of logical channel 12
Tab. 7.5 Example of configuring function
X [i] selected by the Y
Fig. 7.77. Block diagram of mathematical function
X [i] selected by Y
Solution:
We define logical channels in the
Set point value
mode:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
logical channel
such as 1,
–
in the
Name
parameter write
1
,
–
Mode
parameter set as
Set point value
,
140
Logical channel 1
Logical channel 5
Logical channel 8
Logical channel 12
Logical channel 2
Logical channel 3
X[i]
Y
Output
Select Logical channel