User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
7.10.5.
Examples of build-in output configuration
s
7.10.5.1.
Application of the output for R45 modules
See also:
Appendices 8.13. R45, R81, R65, R121 - RELAY MODULES
Appendices
8.7. RT4 , RT6 – RTD MEASUREMENT MODULES
Task:
Let's say that we would like to control temperature (around 30°C) in some room by
switching ON and OFF an electric heater. The hysteresis should be 5°C. The temperature is
measured using a PT100 sensor and
RT4
input module, and let the heater is controlled using
an internal 5A relay (
R45
module).
Solution:
First configure the device as described below, then connect the object and power supply
as shown on
Fig. 7.92.Schematic diagram for the RTD input and Relay output modules
To control temperature in object shown on
, it is necessary to configure one
Logical channel
and
Relay output
.
For reading PT100 sensor temperature:
–
touch screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
Logical channel
such as
1
,
–
in
Name
parameter write
Feedback
,
–
Mode
parameter set as
Hardware input
,
–
Source
parameter set as
Inp.A1 : RTD
162
R
45
4
re
la
y
o
u
tp
u
ts
5
A
/2
5
0V
n01
n02
n03
n04
n05
n06
n07
n08
n09
n10
n11
n12
O
U
T
1
O
U
T
2
O
U
T
3
O
U
T
4
PT100
sensor
Slot A
Inp.A1 : RTD
Inp.A2 : RTD
Inp.A3 : RTD
Inp.A4 : RTD
RT4
4 RTD inputs
I
N
1
I
N
2
I
N
3
I
N
4
n01
n02
n03
n04
n05
n06
n07
n08
n09
n10
n12
n13
n14
n15
n16
n11
Heater
Power supply
L
N
Slot C
O
u
t.
C
1
:
R
e
la
y
Controlled object
Power supply
(depending on version)
1
2
8
5
6
7
3
4
+24V DC ±5%
(
I
max. = 200mA)
digital input
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
SERVICE