6.12.1 Coaxial duct (Ø 60/100mm and Ø 80/125mm)
Coaxial accessories
Description
Code
Ø 60/100 mm
Ø 80/125 mm
Coaxial duct kit
8096250
8096253
Extension W. 1000 mm
8096150
8096171
Extension W. 500 mm
8096151
8096170
Vertical extension W. 140 mm
with smoke analysis take-off
point
8086950
-
Adapter for Ø 80/125 mm
-
8093150
Additional 90° curve
8095850
8095870
Additional 45° curve
8095950
8095970
Tile with joint
8091300
8091300
Roof outlet terminal W. 1284
mm
8091205
8091205
Load loss - Equivalent lengths
Model
Leq (linear metres)
Ø 60/100 mm
Ø 80/125 mm
90° curve
1,5
2
45° curve
1
1
Minimum-Maximum Lengths
Model
Duct Length Ø 60/100
Duct Length Ø 80/125
W
Horizontal
(m)
H Vertical
(m)
W
Horizontal
(m)
H Vertical
(m)
Min. Max. Min. Max. Min. Max. Min. Max.
Vera HE 25
-
6
1,3
8
-
12
1,2
15
Vera HE 30
-
6
1,3
7
-
10
1,2
13
6.12.2 Separate ducts (Ø 60mm and Ø 80mm)
Constructing outlets for separate ducts indicates the use of the
"air-flue split pipe system". This is to be ordered separately
from the boiler and when connected to the other accessories,
from those listed in the table below, completes the smoke-
outlet/ combustion air inlet assembly.
Separate accessories
Description
Code
Diameter Ø 60
(mm)
Diameter Ø 80
(mm)
Air-flue split pipe system
(without take-off point)
8093060
-
Air-flue split pipe system (with
take-off point)
-
8093050
90° curve M-F (6 pieces)
8089921
8077450
90° curve M-F (with take-off
point)
8089924
-
M-F 80/60 reduction
8089923
-
Extension W. 1000 mm (6
pieces)
8089920
8077351
Extension W. 500 mm (6
pieces)
-
8077350
Extension W. 135 mm (with
take-off point)
-
8077304
Wall outlet terminal
8089541
8089501
Internal and external ring
nut kit
8091510
8091500
Inlet terminal
8089540
8089500
45° curve M-F (6 pieces)
8089922
8077451
Manifold
8091400
Tile with joint
8091300
Roof outlet terminal W. 1390
mm
8091204
Inlet/outlet fitting Ø 80/125
mm
-
8091210
Split pipe system
1
2
3
4
Fig. 24
KEY:
1
Split pipe system with take-off point
2
Air inlet
3
Smoke outlet
4
Take-off point for smoke analysis
m
CAUTION
–
The maximum total length of the ducts
, obtained by
adding the lengths of the inlet and outlet pipes,
is determined by the load losses of the individual
accessories used and
must not exceed 15 mm H2O
.
–
For all boiler versions, the total extension
must not
in any case exceed 25 m (inlet) + 25 m (outlet) for
ducts
Ø 80 mm
. The total extension must not exceed
6 m (inlet) + 6 m (outlet) for ducts
Ø 60 mm
, even if
the total load loss is less than the maximum which
can be applied.
Load loss accessory Ø 60 mm
Description
Code
Load loss (mm H
2
O)
Vera HE 25
Vera HE 30
Inlet
Outlet
Inlet
Outlet
Air/smoke split
pipe system
8093060
2,5
0,5
2,5
0,5
90° curve MF
8089921
0,4
0,9
0,5
1,1
45° curve MF
8089922
0,35
0,7
0,45
0,9
Horizontal
extension W. 1000
mm
8089920
0,4
0,9
0,5
1,1
Vertical extension
W. 1000 mm
8089920
0,4
0,6
0,5
0,7
Wall outlet
terminal
8089541
_
1,2
_
1,4
Wall inlet terminal 8089540
0,5
_
0,8
_
Roof outlet
terminal (*)
8091204
0,8
0,1
1,1
0,15
(*) The losses of the roof outlet terminal at inlet include the
manifold code 8091400.
NOTE:
for the boiler to operate correctly it is necessary that a
minimum distance of 0.50 m of the duct is respected with a 90°
inlet curve.