background image

8

between. This could occur in particu-
lar in systems presenting high head
losses.  At  each  restart  after  the
period of slow ignition, the boiler will
set  itself  for  about  1  minute  at  the
minimum  modulation  pressure,  and
will  then  move  to  the  heating  pres-
sure value set.
When  the  connecting  link  is  inser-
ted, both the programmed technical
pause and the period of operation at
minimum  pressure  in  the  start-up
phase will be cancelled. 
In  this  case,  the  times  elapsing
between turning off and subsequent
re-ignition will depend on a tempera-
ture  difference  of  8°C  detected  by
the SM sensor.

NOTE:  It  is  essential  that  the  opera-
tions described above be carried out
by authorized technical staff.

3.2TEMPERATURE SENSORS

The 

“SUPER FOUR”

boilers are equip-

ped with sensors for detecting tempe-
rature:
– C.H.  sensor,  located  on  the  outlet

pipe of the primary exchanger (SM)

– D.H.W.  sensor  located  on  the  hot

water storage boiler unit (SS).

The  sensors  are  NTC  mod.  ST03
ones and are interchangeable. 

Table  2 shows  the  resistance  values
that  are  obtained  on  the  sensors  as
the temperature varies.

NOTE:  Should  the  SM  sensor  be
shorted,  the  boiler  will  not  operate
either  for  central  heating  or  for  hot
water; should, instead, the SS sensor
be  shorted,  the  boiler  will  operate
only for central heating.

3.3

ELECTRONIC IGNITION

The 

“SUPER  FOUR”

version  boilers

are of the type with automatic ignition
(without pilot burner). 
They  are  therefore  equipped  with  FM
31 electronic control and protection (6
fig.  9).  Ignition  and  flame  detection  is
controlled  by  two  electrodes  located
on the burner. 
These  guarantee  maximum  safety
with intervention times, for accidental
switching  off  or  gas  failure,  of  within
one second.

3.3.1

Operating cycle

Turn  the  switching  knob  located  on
the control board to either SUMMER
or WINTER to check for presence of
voltage  supply  (green  warning  lamp
lights up). 
The  boiler  is  now  ready  to  start
working upon demand for heating or
drawing  off  of  domestic  water;  a
discharge current is sent to the igni-
tion  electrode  through  the  FM  31
programmer, and the gas valve opens
at the same time.
Burner  ignition  normally  takes  place
within  2  or  3  seconds  starting  from
the  moment  when  the  discharge  cur-
rent  reaches  the  ignition  electrode.
However, it is possible for ignition failu-
res  to  occur,  with  consequent  activa-
tion of signal indicating that the equip-
ment has “locked out”. 
Failures  may  be  due  to  one  of  the  fol-
lowing causes:

Gas failure

The appliance runs through the cycle
normally  sending  electric  power  to
the ignition electrode. 
The  electrode  continues  spark
discharge for a maximum of 10 sec.
If  the  burner  does  not  ignite,  the
equipment “locks out”. 

This may occur upon first ignition or
after  long  periods  of  boiler  lay-off
when there is air in the pipes. It may
be  caused  by  the  gas  tap  being  clo-
sed  or  by  one  of  the  valve  coils
having a break in the winding, so that
the valve cannot open.

Ignition electrode fails to spark

In the boiler, only the gas to the bur-
ner  is  seen  to  open.  After  10  sec.
the equipment “locks out”.

This  may  be  due  to  a  break  in  the
wire of the electrode, or the wire not
properly  fastened  to  the  equipment
electric  terminal;  or  else,  the  tran-
sformer has burnt out.

No detection of flame

The  continuous  spark  discharge  of
the electrode is noted starting from
ignition, even though the burner is lit.
After 10 seconds have elapsed, the
sparks  cease,  the  burner  goes  out,
and  the  warning  light  indicating
equipment “lock-out” lights up.

This occurs when the position of line
and neutral has not been respected
on the terminal block.
There  is  a  break  in  the  wire  to  the
sensing  electrode,  or  the  electrode
itself is touching earth; the electrode
is worn out and needs replacing.

When there is a sudden voltage failure,
the  burner  shuts  out  immediately;
when power supply returns, the boiler
will start up again automatically.

3.4

SMOKE PRESSURE 
SWITCH

The smoke pressure switch is located
inside the sealed- room (7 fig. 3). 
To gain access to the pressure switch,
first you must release the four hinges
and  remove  the  fixing  screw  of  the
front wall. 
A Venturi tube system, fastened inside
the fan unit and connected to the pres-
sure  switch  by  means  of  two  silicone
pipes,  ensures  start-up  of  the  burner
only  when  the  fan  is  operating.
Impurities  and  possible  formations  of
condensate,  which  are  more  likely  in
cold  periods  of  the  year,  could  cause
the  pressure  switch  not  to  function
and the boiler to fail to start. The pres-
sure switch is set in the factory at the
optimal values of 8-9 mm H

2

O. 

This  is  able  to  guarantee  operation  of
the boiler even with air intake and flue
outlet pipes have the maximum limit of
length allowed.

3.5

WATER FAILURE 
SAFETY DEVICE

The  boiler  is  equipped  with  a  water
pressure  switch  (8  fig.  13)  set  at  0.6
bar,  which  goes  into  action,  blocking
boiler operation, whenever the pressu-
re inside the boiler is less than the cali-
bration value. 
When  the  pressure  switch  trips,  a
red warning lamp starts flashing (11
fig. 11). To restore burner operation,
turn  the  charge  cock  and  bring  the
pressure  back  to  a  value  between 

1

and 

1.2 bar

.

Temperature °C

Resistance 

20

12,000

30

8,300

35

6,900

40

5,800

45

4,900

50

4,100

55

3,500

60

3,000

70

2,200

80

1,700

TABLE 2

Summary of Contents for Super four

Page 1: ...Super four Installation and servicing instructions GB...

Page 2: ...Open the gas tap and check the soundness of the connections including that of the burner Purge the system bleeding off the air present in the gas pipe by operating the air relief valve on the gas valv...

Page 3: ...uct 60 100 Fig 1 The gas consumptions refer to the calorific value at standard conditions at 15 C 1013 mbar SUPER FOUR Heat output Maximum kW 28 5 Minimum kW 15 1 Heat input Maximum kW 31 6 Minimum kW...

Page 4: ...n vessel 23 Magnesium anode 24 Air relief valve 25 Boiler unit safety valve 26 Frost stat 27 D H W isolation valve 28 Gas cock 29 C H return isolation valve 30 C H flow isolation valve 1 4 FUNCTIONAL...

Page 5: ...e boiler with serious consequences IT IS ABSOLUTELY ESSENTIAL THAT THE WATER USED FOR THE CENTRAL HEATING SYSTEM SHOULD BE TREA TED IN THE FOLLOWING CASES very extensive system with high con tents of...

Page 6: ...cations of possible solutions Table 1 gives the minimum distances to be observed with refe rence to the type of building shown in fig 6 4 Fig 6 KEY A Elbow flange B Junction collar C Outer duct D Alum...

Page 7: ...V 50 Hz single phase through a fused main switch with at least 3 mm spacing between contacts You are recommended to install a room temperature thermostat to ensure bet ter regulation of temperature a...

Page 8: ...rode TS 100 C safety stat TA Room stat M Modulating coil PA Water pressure switch PI C H circulating pump PB D H W circulating pump SM Heating sensor blue SS D H W sensor red C Four way switch FA EMC...

Page 9: ...ated so as to obtain a pressure of approx 3 5 mbar at the burner for natural gas and 7 mbar for L P G G30 G31 To increase pressure turn the trimmer clockwise to reduce pres sure turn the trimmer count...

Page 10: ...ic power to the ignition electrode The electrode continues spark discharge for a maximum of 10 sec If the burner does not ignite the equipment locks out This may occur upon first ignition or after lon...

Page 11: ...00 Portata l h Prevalenza residua mbar MURELLE BN AVANT BF RESIDUAL HEAD mbar FLOW RATE l h Fig 14 Fig 13 KEY 1 Gas cock 2 Union 3 C H return cock 4 C H flow cock 5 D H W inlet cock 6 D H W safety val...

Page 12: ...ream of the gas valve remove the plastic cap 1 set the switching knob to SUMMER and open the D H W tap at a high flow rate with the boiler lit using a 10 span ner turn the nut 3 to arrive at the maxim...

Page 13: ...e main nozzles 3 located on the burner manifold 1 inserting the copper washer 2 Use a 7 span ner to perform this operation reassemble all the parts proceeding in reverse order remove the L P G MET con...

Page 14: ...moke pressure switch Replace electronic card Check if SM is interrupted Fan turns but burner does not start Check whether connection tubes of smoke pressure switch PF are obstructed and if necessary c...

Page 15: ......

Page 16: ...Cod 6258908A Documentation Dpt Sime Ltd Unit D2 Enterprise Way Bradford Road Idle Bradford BD10 8EW Tel 0870 9911114 Fax 0870 9911115 www sime ltd uk e mail enquiries sime ltd uk...

Reviews: