2.5.1 Sizing of flue
The.correct.sizing.of.the.flue.is.an.essen-
tial. condition. for. efficient. boiler. opera-
tion..
The.main.factors.to.be.taken.into.consi-
deration. for. calculating. the. section. are.
the. heat. input. of. the. boiler,. the. type. of.
fuel,. the. percentage. of. CO2,. the. mass.
flow.of.smoke.at.nominal.load,.the.tem-
perature.of.the.smoke,.the.roughness.of.
the.internal.wall,.and.the.effect.of.gravity.
on. the. draught. pressure,. which. must.
take.into.account.the.external.tempera-
ture.and.the.altitude..
2.6
ELECTRICAL
CONNECTION
The. boiler. is. supplied. with. an. electric.
cable.. Should. this. require. replacement,.
it. must. be. purchased. exclusively. from.
SIME..
The. electric. power. supply. to. the. boiler.
must.be.230V-50Hz.single-phase.throu-
gh. a. fused. main. switch,. with. at. least. 3.
mm.spacing.between.contacts..
The. room. stat. must. be. class. II. as. spe-
cified. by. standard. EN. 60730.1. (clean.
contact).
NOTE: Device must be connected to an
efficient earthing system.
SIME declines all responsibility for
injury or damage to persons, animals
or things, resulting from the failure
to provide for proper earthing of the
appliance.
Always turn off the power supply before
doing any work on the electrical panel.
Tetto piano
0,50 m
0,50 m
Volume
tecnico
> 5 m
≤
5 m
Colmo
> 1,50 m
≤
1,50 m
Zona di reflusso
1,50 m
2 m min.
0,50 m oltre il colmo
45
°
Tetto a 45°
Colmo
> 1,30 m
≤
1,30 m
Zona di reflusso
0,80 m
1,20 m min.
0,50 m oltre il colmo
30
°
Tetto a 30°
Fig..4
Flat roof
30° roof
45° roof