Example of allowable installation
“35”
calculation in that the sum of the head losses of the
single fittings is less than 15 mm H
2
O:
Inlet
Outlet
9 m horizontal pipe ø 80 x 0.25
2.25
–
9 m horizontal pipe ø 80 x 0.25
–
2.25
n° 2 90° elbows ø 80 x 0.30
0.60
–
n° 2 90° elbows ø 80 x 0.40
–
0.80
n° 1 terminal ø 80
0.15
0.50
Total head loss
3.00
+
3.55
=
6.55 mm H
2
O
TABLE 2
Accessories ø 80
Total head loss (mm H
2
O)
35
Inlet
Outlet
Coaxial duct kit
–
–
90° elbow MF
0.30
0.40
45° elbow MF
0.25
0.25
Extension L. 1000 (horizontal)
0.25
0.25
Extension L. 1000 (vertical)
0.25
0.25
Wall terminal
0.15
0.50
Wall coaxial exhaust *
Roof outlet terminal *
1.50
0.20
*
The loss of the accessorie in aspiration concludes the collector code 8091400/01
Fig. 6/a
9
C53
C33
C43
C83
11
10
3
1
1
3
3
2
1
2
6
1
3
11
10
3
7
3
3
3
6
2
3
3
max 0,5 m
max 0,5 m
C13
4
3
2
6
5
3
1
12
12
12
C13
3
2
3
1
14
12
13
12
Fig. 6/b
LIST OF ø 80 ACCESSORIES
1
--------
2
Additional 90° MF curve code
8077450 (6 pz.)
3 a
Extension
L. 1000 code 8077351 (6 pz.)
3 b
Extension
L. 500 code 8077350 (6 pz.)
4 Exhaust terminal, code 8089501
5 Kit with internal/external ring nuts, code 8091500
6 Suction terminal, code 8089500
7
Additional 45° MF curve code
8077451(6 pz.)
9 Manifold, code 8091400
10
Tile for joint code
8091300
11
Terminal for roof exit
L. 1381 code 8091204
12 --------
13 Union suction/exhaust code 8091401
14 Coaxial exhaust ø 80/125 L. 885 code 8091210
NOTE
Before connecting accessories, it is always
advisable to lubricate the internal part of the
gaskets with silicon products. Avoid using oils
and greases.
IMPORTANT: In type C53 the outlet
and inlet flues must not come out
on opposite walls.