Control Unit 

GFC 32

 

 

 

SIMATEK A/S 

www.simatek.com 
Hotline: +45 4046 7525 
[email protected] 

 
 

Doc. No.: 1400004_EN 

Rev.: - 

Date: 05.2017 

 

6.

 

Settings 

 

6.1

 

Voltage selection 

 

CHECK: 

1.

 

That the Simatek GFC 32 does not have power (switch on/off [1] on 0 and terminals [4] disconnected). 

2.

 

That the supply voltage indicated on the yellow label [22] as “IN” corresponds to the available supply voltage 

(Voltage and frequency). 

3.

 

That the supply voltage to valves indicated on the yellow label [22] as “OUT” corresponds to the 

voltage/frequency indicated on the coils. 

 

If these 3 conditions are met, go to paragraph 6.2. 

Otherwise, carefully follow the procedure below!  

 

A.

 

Supply voltage selection 

 

1.

 

Unscrew the 2 screws [21] (optional), and open the Simatek GFC 32 transparent cover.  

2.

 

Remove the 4 screws of the front panel. Lift the front panel (do not remove it as it is connected to the base of 

the enclosure!). 

3.

 

Check that the supply voltage, selectable by jumper [5], corresponds to the one available from the supply 

voltage (e.g. both are set to 230 V). 

4.

 

Should the two voltages be different, move the jumper [5] in order to select the same supply voltage.  

5.

 

Go to point 6.1.B. 

 

B.

 

Selection of power supply to the valves 

 

1.

 

Check that the supply voltage to the valves selectable by jumpers [6] and [6A] corresponds to the supply 

voltage indicated on the coils of the valves (e.g. both are set to 24 V).  

2.

 

Should the two voltages be different, move the jumpers [6] and [6A] in order to select the same supply voltage 

as indicated on the coils. 

3.

 

Caution: both jumpers [6] and [6A] must correspond to the same voltage! 

4.

 

Go to point 6.1.C. 

 

C.

 

Selection of power supply frequency to the valves (AC/DC) 

 

1.

 

Make sure that the output frequency to the valves, selectable by jumpers [8], corresponds to the value 

indicated on the coils (e.g. both are set to AC). 

2.

 

Should the two frequencies are different, move the jumpers [8] in order to select the same frequency as 

indicated on the coils. 

3.

 

Put the front panel back in place and fasten the 4 screws.  

4.

 

Close the transparent cover by means of the 2 screws [21] (optional). 

 

 

 

Never select 115 or 230 V/DC for output! 

 

Summary of Contents for GFC 32

Page 1: ...Manual Control Unit GFC 32 1400004_EN 05 2017 ...

Page 2: ...croprocessor failure alarm 9 12 Troubleshooting 10 13 Fuse table 10 14 Factory settings Program menu 11 15 Legend 12 16 Simatek GFC 32 20 General assembly 13 17 Electric diagram for Simatek GFC 32 20 valves 14 18 Declaration of Conformity 15 NOTE Figures shown inside square brackets refer to positions on page 13 ATTENTION Before use read the instructions thoroughly to acquire sufficient knowledge ...

Page 3: ... Temperature Storage 20 C 80 C Operating 10 C 50 C with duty cycle 30 Voltage available Input 230 V 10 50 60 Hz Output 115 230 24V AC 24 V DC Input 115 V 10 50 60 Hz Output 115 24V AC 24 V DC See page 6 6 1 Special version 24V DC 24V DC Power consumption Without output 2 5 VA Output max 25 VA AC or 20 W DC Pulse time 0 01 9 99 sec Pause time 1 999 sec Max duty cycle 30 Remote control Activated via...

Page 4: ...d A disconnecting switch has to be installed on the power line before the control unit Do not attempt to repair the control unit contact Simatek All wiring has to be carried out by a qualified electrician to prevent any risk of fire and electrical shocks Control unit wiring has to be performed in such a way that the different types of cables power relay s contact valve output 4 20 mA output are ke...

Page 5: ... switch 1 on 0 and terminals 4 disconnected 3 Extract the removable terminals 2 4 Check that the supply voltage to valves indicated on the yellow label 22 as OUT corresponds to the voltage frequency as indicated on the coils 5 Connect the valves to the terminal blocks 2 between terminal C and the numbered outputs 6 Earthing 3 of the valves is necessary when output voltage is 48 V 7 NEVER connect t...

Page 6: ...ds to the one available from the supply voltage e g both are set to 230 V 4 Should the two voltages be different move the jumper 5 in order to select the same supply voltage 5 Go to point 6 1 B B Selection of power supply to the valves 1 Check that the supply voltage to the valves selectable by jumpers 6 and 6A corresponds to the supply voltage indicated on the coils of the valves e g both are set...

Page 7: ... 5 Press SELECT MENU 9 The display 7 will show the letter E run and the number of the valve which is going to be activated the cleaning cycle starts LED PULSE 11 will indicate that a valve is activated LED PAUSE 12 will indicate that the Simatek GFC 32 is waiting to activate the next valve NOTE Valves are pulsed from output No 1 onwards The Simatek GFC 32 automatically skips any disconnected outpu...

Page 8: ... remove the residual dust of the filter Shut down cleaning is started each time the fan is switched off In order to activate Shut down cleaning 1 Select Pause Time and number of cycles of Shut down cleaning see paragraph 6 2 Unscrew and remove the terminals cover 20 3 Bring an external no load and normally closed NC contact to terminals Fan 36 and Common 37 from the fan switch 4 Replace the termin...

Page 9: ...tify the faulty valves 1 Press the key 10 The display 7 will show the letter A followed by the number of the output in alarm 2 Keep pressing the key 10 in order to identify all of the outputs in alarm 3 Press key 10 to go back to E run 4 Perform the required maintenance 5 Press Alarm reset 19 The alarm is eliminated as the fault has been rectified To have remote Alarm signal connect to the relay s...

Page 10: ...ply voltage to valves is different from voltage indicated on the coils Move jumpers 6 and 6A in order to select the same power supply as indicated on the coils LED WD 18 is off Microprocessor failure Contact Simatek LED REMOTE 35 is off and Simatek GFC 32 is in block The bridge on terminals Remote 26 has been removed Replace the bridge on terminals 26 Contact on terminals Remote 26 has been opened...

Page 11: ...leaning The pause time during shut down cleaning may be set as required according to the properties of the dust in question however the pause time must be correspond to the compressor capacity 14 4 Shut down cycles Bag cleaning will continue during the set number of cycles first valve to last valve after connection between Fan 36 and Common 37 fan stopped Any equipment for removal of the separated...

Page 12: ...selection to valves 9 Push button Select Menu 10 Push buttons 11 LED Pulse 12 LED Pause 15 LED Low pressure 17 LED Alarm 18 LED WD watch dog 19 Push button Reset 20 Terminals cover 21 Transparent cover fixing screws optional 22 Yellow label indicating IN OUT voltage frequency 23 Fuse 24 Relay terminals 25 Product code and serial number 26 Terminals Remote 29 Terminal Low pressure 31 External conta...

Page 13: ...Control Unit GFC 32 SIMATEK A S www simatek com Hotline 45 4046 7525 aftersales simatek dk 13 Doc No 1400004_DK Rev Date 05 2017 16 Simatek GFC 32 20 General assembly ...

Page 14: ...Control Unit GFC 32 SIMATEK A S www simatek com Hotline 45 4046 7525 aftersales simatek dk 14 Doc No 1400004_EN Rev Date 05 2017 17 Electric diagram for Simatek GFC 32 20 valves ...

Page 15: ...Control Unit GFC 32 SIMATEK A S www simatek com Hotline 45 4046 7525 aftersales simatek dk 15 Doc No 1400004_DK Rev Date 05 2017 18 Declaration of Conformity ...

Reviews: