SIM2W-FLOOD-I
TWO WAY WIRELESS FLOOD DETECTOR
INSTALLATION INSTRUCTIONS
P/N 710XXXX Rev A D.Z
INTRODUCTION
The SIM2W-FLOOD-I is an advanced flood
detector with integrated RF transceiver designed
to be a fully supervised low-current device
FEATURES
Two Way Wireless secured RF protocol
Low current Technology
Powered by a single 3V Lithium battery
Battery life: more than 5 years
Tamper Open/Close transmission
Supervision transmission
Battery status send on every transmission
Range up to 500m on open space.
Unique ID number
Front and back tamper.
Alarm trigger by the wired contact sensor which
is located at the end of the wired cable
4
5
6
OPERATION
The SIM2W-FLOOD-I detector transmits the
following events data:
SUPERVISION
- a periodical transmission time
which is configurable
indicates detector’s
presence.
ALARM
- Alarm transmission triggered by Golden
contacts pins located at the end of the external
cable , The fluid has to reach the two exposed
golden contacts
LOW BAT
– Whenever the battery reaches a pre-
set low level (~2.4V) Battery Low signal will be
sent with the next scheduled message
(Supervisor, Alarm, etc.).
TAMPER
– Whenever the FW2-TEMP cover is
removed or tore off wall, a message will be
transmitted with “Tamper” signal.
FIG. 1 - REMOVAL OF FRONT COVER
FIG. 2 - BATTERY PLACEMENT
7
8
9
Fig. 3 - CIRCUIT LAYOUT
FIG. 4
– MOUNT FORM
Fig. 5 - KNOCKOUT HOLES
10
11
12
MOUNTING THE DETECTOR
A.
Mount the SIM2W-FLOOD-I sensor unit.
B.
To remove the front cover, unscrew the holding
screw (Fig.1), insert a flat screwdriver in the
slot between the front and the bottom while
pushing and twisting it gently until the front
cover is disengaged. (Fig. 1)
C. Remove Printed Circuit board from the unit base
D. Mount the base at 60cm above the sensor (Fig. 4),
E. place all 3 screws (Fig.5) and make sure you tighten the
tamper screw (the middle screw) easily, so the back
tamper switch will press the switch successfully when
PCB is placed back - over winding may result in false
mechanical adaptation and lack of tamper press
MOUNTING THE DETECTOR
F. Install the Printed Circuit board back into the base of
the wireless unit.
G. Connect the two wires coming form the sensor to the
Terminal block (Fig
4).
The fluid has to reach the two
exposed Golden contacts at the bottom side of the
sensor in order to give an alarm
Use only the supplied screws and plugs.
H
. Install battery (Fig.2) according to the polarity (-) (+)
indications.
Risk of explosion if battery is replaced by an incorrect
type.
Use only batteries delivered by the supplier.
I
. Place the cover by inserting it back in the appropriate
closing pin and screw the holding screw.
ID REGISTRATION
Refer to the system transceiv
er’s installation instructions
and follow the “learning” detector IDs.
Place battery as instructed & wait until LED stops blinking.
Make sure that the transceiver is on learning mode.
Generate a transmission by pressing and releasing tamper
switch of the SIM2W-FLOOD-I.
Note the LED indications on the device:
Green/Red LED flashes alternately
– for 5 sec
TEMP was registered successfully.
Green LED blinks periodically
–
Device was not sighed into panel.
Repeat registration process
Red LED blinks
– for over 20sec
Battery voltage is critically low. Replace battery
Antenna
Contacts
wire cable
Input
Battery
Tamper
Use for flat wall
mounting
Place the Flood
unit near this
marking
(Do not over tighten)