SIM2W-FLOOD-I 

TWO WAY WIRELESS FLOOD DETECTOR 

 
 
 

 

INSTALLATION INSTRUCTIONS 

P/N 710XXXX Rev A D.Z

 

 

INTRODUCTION

 

The SIM2W-FLOOD-I is an advanced flood 

detector with integrated RF transceiver designed 

to be a fully supervised low-current device  

 

 

 

FEATURES

 

  Two Way Wireless secured RF protocol 

  Low current Technology 

  Powered by a single 3V Lithium battery 

  Battery life: more than 5 years 

  Tamper Open/Close transmission 

  Supervision transmission 

  Battery status send on every transmission 

  Range up to 500m on open space. 

  Unique ID number 

  Front and back tamper. 

  Alarm trigger by the wired contact sensor which 

is located at the end of the wired cable 

4

 

 

5

 

 

6

 

OPERATION 

The SIM2W-FLOOD-I detector transmits the 
following events data: 

 
SUPERVISION

 - a periodical transmission time 

which is configurable 

indicates detector’s 

presence. 
 

ALARM

 - Alarm transmission triggered by Golden 

contacts pins located at the end of the external 
cable , The fluid has to reach the two exposed 
golden contacts  

 
LOW BAT

 

– Whenever the battery reaches a pre-

set low level (~2.4V) Battery Low signal will be 
sent with the next scheduled message 
(Supervisor, Alarm, etc.). 
 

TAMPER

 

– Whenever the FW2-TEMP cover is 

removed or tore off wall, a message will be 
transmitted with “Tamper” signal. 
 

 

FIG. 1 - REMOVAL OF FRONT COVER 

 

 

 

FIG. 2 - BATTERY PLACEMENT 

 

 

7

 

 

8

 

 

9

 

Fig. 3 - CIRCUIT LAYOUT 

                           

 

 

FIG. 4 

– MOUNT FORM   

 

 

 

Fig. 5 - KNOCKOUT HOLES 

   

 

10

 

 

11

 

 

12

 

MOUNTING THE DETECTOR 

A. 

Mount the SIM2W-FLOOD-I sensor unit. 

B. 

To remove the front cover, unscrew the holding 

screw (Fig.1), insert a flat screwdriver in the 

slot between the front and the bottom while 

pushing and twisting it gently until the front 

cover is disengaged. (Fig. 1) 

C. Remove Printed Circuit board from the unit base 

D. Mount the base at 60cm above the sensor (Fig. 4), 

 

E. place all 3 screws (Fig.5) and make sure you tighten the 

tamper screw (the middle screw) easily, so the back 

tamper switch will press the switch successfully when 

PCB is placed back - over winding may result in false 

mechanical adaptation and lack of tamper press 

 

 

MOUNTING THE DETECTOR 

 
 

F. Install the Printed Circuit board back into the base of 

the wireless unit. 

G. Connect the two wires coming form the sensor to the 

Terminal block (Fig

 4). 

The fluid has to reach the two 

exposed Golden contacts at the bottom side of the 
sensor in order to give an alarm 

 

 

Use only the supplied screws and plugs.  

H

. Install battery (Fig.2) according to the polarity (-) (+) 
indications. 

 

 

Risk of explosion if battery is replaced by an incorrect 

type.  

      Use only batteries delivered by the supplier. 

 I

. Place the cover by inserting it back in the appropriate    

 

  

closing pin and screw the holding screw. 

 
 
  
     

 
 

 

ID REGISTRATION 

Refer to the system transceiv

er’s installation instructions 

and follow the “learning” detector IDs.  

 

Place battery as instructed & wait until LED stops blinking. 
Make sure that the transceiver is on learning mode. 
Generate a transmission by pressing and releasing tamper 
switch of the SIM2W-FLOOD-I. 
 
Note the LED indications on the device:  

  Green/Red LED flashes alternately 

– for 5 sec     

TEMP was registered successfully. 

  Green LED blinks periodically 

– 

Device was not sighed into panel.   
Repeat registration process 

  Red LED blinks 

– for over 20sec 

Battery voltage is critically low. Replace battery

 

 

 

 

 

 

 

Antenna

 

Contacts 
wire cable 
Input 

 

Battery

 

Tamper

 

Use for flat wall 
mounting 

 

Place the Flood 
unit near this 
marking

 

(Do not over tighten) 

 