MESH-CEFL

Ceiling Flush Mount Passive Infra Red 

(PIR) Occupancy Detector & Photocell

Input: 100-240 Vac  50/60Hz                             

PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: MESH-CEFL is compatible with any qualifi ed Bluetooth mesh components and commissioning tools. 

We recommend Silvair Commissioning as a reliable solution.

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388  E-mail: [email protected]    

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

11/10/19 

INS372 MESH-CEFL  (Issue 04)

TECHNICAL DETAILS

INPUT

Voltage:

100 - 240Vac

Frequency:

50/60Hz

Max. mains current:

20mA

Standby current:

14mA

RADIO TRANSCEIVER

Operating frequencies: 2.4... 2,480 GHz
Max. output power:

+4 dBm

LUX PARAMETERS

Range:

5 - 2000 lux

OPERATING CONDITIONS 

Note: The temperature difference between the 

detection target and the background must be at 

least 4 °C.

Ambient temperature:

-20... +40 °C (lout 

20mA)

Storage temperature:

-25... +75 °C

Max. relative humidity:

0... 80%, non cond.

CONNECTORS

Terminal block 

Wire size:

0.5mm

2

 - 2.5mm

2

 solid 

or stranded

Wire strip length:

6-7mm

Tightening torque:

0,4 Nm/4 Kgf.cm

MECHANICAL DATA

Dimensions:

79mm x 85mm x 

85mm

Weight:

97g (unpacked)

Degree of protection:

IP40

Protection class:

Built-in Class 2

Material (casing)

Flame-retardant 

polycarbonate

Finish / Colour

Matt /White (RAL 9003)

Protection class:

Built-in Class 2

CONFORMITY AND STANDARDS
EMC emission: 

EN 301 489-1 V2.2.0,  

EN 301 489-17 V3.1.1, 

EN 55032: 2015,  

EN61000-3-2: 2014, 

EN61000-3-3: 2013

EMC immunity:

EN 301 489-1 V2.2.0,  

EN 301 489-17 V3.1.1

Environment: 

Complies with WEEE and RoHS directives

CB scheme:

IEC60669-1:1998, 

IEC60669-1:1998/AMD1:1999, 

IEC60669-1:1998/AMD2:2006, 

IEC60669-2:2002, 

IEC60669-2-1:2002/AMD1:2008,

This fl ush mounted MESH-CEFL is suitable for 
easy mounting through a 73/75mm diameter hole 
into a ceiling void which is at least 78mm deep. 
Confi gurable for any room occupancy style, via the 
Silvair  Platform (App and Web).

INSTALLATION

To be installed by a competent person with 
reference to BS 7671 or equivalent local standards. 
If in doubt consult a qualifi ed electrician.

•  Plan where the MESH-CEFL is to be located 

(see diagram 1). Switch off supply and check 
for hidden cables and pipes. Make a 73/75mm 
diameter hole through a standard ceiling board.

•  The MESH-CEFL should be connected as 

shown in diagram 2:

  L - Live in.   N - Neutral in.

•  Ensure both springs are fi tted to the moulding in 

the correct orientation (see diagram 3).

•  Push the MESH-CEFL into the ceiling void, 

making reference to diagram 4.

OPERATION

To check the operation of the MESH-CEFL:

•  Turn on the supply then after 20 seconds if the 

sensor has recognised movement of a person 
within its zone of detection the integral red 
LED on MESH-CEFL will stay illuminated for 4 
seconds before the red LED turns off.

•  Thereafter, every time movement is detected 

by MESH-CEFL the integral red LED will stay 
illuminated for 4 seconds. 

The control also features adjustable time out (time 
lag) control and daylight threshold control which 
are confi gured via the Silvair Platform.

PRECAUTIONS

•  Do not place the MESH-CEFL near heat 

sources, fans or in ventilated ceiling voids.

•  MESH-CEFL can be wired in parallel (sharing 

the same Live and Neutral).

•  Do not place close to, or positioned such 

that, any light source points directly into the 
MESH-CEFL. 

•  Ensure wires and cables are securely held within 

the connection terminals.

•  The MESH-CEFL should be protected by a 5 or 

6 Ampere mcb or fuse.

• 

Disconnect the MESH-CEFL from the 
circuit before performing insulation testing 
of the wiring circuit.

DIAGRAM 2

Suggested typical wiring

N

L

230 Vac

5A or 6A MCB

or fuse

L

N

N

L

L - Live in. N - Neutral in.

Two neutral and two live terminals

are available for easy ‘loop in’ and 

‘loop out’ connection.

Squeeze spring coils together and fi t 
onto each of the two lugs in turn.
Repeat on opposite side of product .

DIAGRAM 3

Ceiling void at least 78mm deep. 75mm circular hole cut for MESH-CEFL.

DIAGRAM 4

up to 5m
up to 7m

Strong detection zone 

i.e. person moving arm 

or walking towards PIR

For optimum coverage recommended 

mounting height: 2.4 to 5m

Secondary detection

zone i.e. person walking 

perpendicular to PIR

DIAGRAM 1

DIMENSIONS, HALL EFFECT AND 
FACTORY RESET:

See overleaf for details.