background image

 
DG558 Technical reference manual 
 
 
 

1. Product description 
 

 

DG558MA04D1A01  is  a  Qualified  Bluetooth  Mesh®  control  unit  for  lighting  drivers  with

  DALI

®

  dimming 

interface

.  

 
DG558MA04D1A01 provides internal DALI bus power supply (10VDC) with a maximum current of 20mA  
(i.e. up to 10 connected DALI devices). 
 
DG558MA04D1A01 is an easy and smart way to provide Bluetooth Mesh® network capabilities to standard 
DALI control gears. 
 
It allows to communicate with DALI Control Gear over the DALI protocol by converting Standard Bluetooth 
Mesh commands to DALI Commands. 
 
Supported features are: 
 

  Broadcasting DAPC (direct arc power control) message to DALI Control Gears 

 

  Reading status information from DALI Control Gear to report failures. 

 

  Fast Fade Time support (default set to 50ms) 

 

  Supported failures include: 

 

  DALI Control Gear Failure 

  DALI Light Source Failure 

  DALI Limit Error 

  DALI No Response Warning 

  DALI No Response Error 

  DALI Bus Short Error 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                

[email protected]        www.dglight.eu

                                  page 

3

 

Summary of Contents for DG558MA04D1A01

Page 1: ...July 2019 DG558MA04D1A01 Technical reference manual Date 01 07 2019 Version 201907 www dglight eu...

Page 2: ...rotected from copying under the provisions of copyright laws The copyrights belong to DG Light Any unauthorized copying alteration distribution transmission performance display or other use of this ma...

Page 3: ...al Table of Contents Table of Contents 2 1 Product description 3 2 Technical data 4 3 Wiring diagram and description 5 4 Installation and precautions 6 5 Commissioning by SILVAIR 7 6 Contact 8 info dg...

Page 4: ...to standard DALI control gears It allows to communicate with DALI Control Gear over the DALI protocol by converting Standard Bluetooth Mesh commands to DALI Commands Supported features are Broadcastin...

Page 5: ...d DALI control gears Operating conditions Ambient temperature ta 20 50 C Max case temperature tc 70 C Storage temperature 25 70 C Max relative humidity 0 80 non cond Connectors L N Wire range solid st...

Page 6: ...tus LED see Note 1 RESET To trigger factory reset please place a magnet near RESET for at least 5 seconds until LED1 will start blinking as unprovisioned according to Note1 DALI DALI Bus interface and...

Page 7: ...ass II device Use double insulated wires or an external mounting box if the device is not mounted inside another insulated device Make sure that the ambient temperature does not exceed the specified m...

Page 8: ...eb app which is used off site to manage lighting installation projects plan commissioning along with mapping zones on a floor within a building setting up control scenarios for zones and managing user...

Page 9: ...DG558 Technical reference manual Contact info dglight eu www dglight eu 39 011 9040938 Our office Via Giaveno 20 10040 Cumiana TO ITALY info dglight eu www dglight eu page 8...