151161
4-14
remove both the AC power and the battery to make the 5495 recognize the new settings.
Figure 4-7 Setting DIP Switches 1-3
Figure 4-8 Setting DIP Switches 1-3 (Continued)
Note:
For 100 mS input signal debounce with no synchronization DIP switches 6 and 7 must be turned On.
4.8.1.1
Input/Output Configurations That Select ANSI Temporal-Coded
Outputs
The DIP switch settings marked with an asterisk (*) in Figure 4-7 and Figure 4-8 are designed to produce ANSI
temporal-coded outputs from a constant input. The figures shown below compare the output patterns of