SILENT KNIGHT 5104B Installation And Operation Manual Download Page 22

Model 5104B Installation Manual

151053-L8

 3-14

3.11 Supplemental Notification Appliance Installation

The Supplemental notification circuit supplies a DC output that can be used to power a DC audible device during 
an alarm condition. Pressing the reset / silence switch will silence the output. Refer to section 6.2.7, Step 14, to 
program the notification circuit’s supervision properties.

3.11.1 Non-Supervised Notification Appliance Wiring

Figure 3-9 illustrates how to wire a non-supervised notification device to the control panel.

Figure 3-9  Non-Supervised Alarm Bell Wiring

Note: Polarities shown in Figure 3-9 illustrate the polarity in an alarm condition. Under normal conditions the 

polarity of terminals 21 and 22 are reversed.

Note: Per NFPA 72 Requirements the means of silencing a Supervisory Signal or Alarm must be located within 

a locked cabinet. To comply, DO NOT install the reset/silence switch extruder or remove the switch knock-
out.

Wheelock

Model MB-G10-12-R

12 VDC Bell

Summary of Contents for 5104B

Page 1: ...Installation and Operations Manual Model 5104B Fire Communicator Document 151053 L8 05 05 2014 Rev F3 P N 151053 L8 F3 ECN 14 0068...

Page 2: ...itive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic a...

Page 3: ...ator LEDs L6 L7 3 5 3 4 2 3 Overcurrent LED Indicators L1 L2 3 6 3 4 3 Reset Silence Switch 3 6 3 4 4 Cable Connectors P1 P2 and P3 3 6 3 4 5 On board Piezo Sounder 3 6 3 5 Calculating Current Draw an...

Page 4: ...ts 6 1 6 2 5230 Programming 6 1 6 2 1 Default User Codes 6 1 6 2 2 How to Enter and Exit Program Mode 6 1 6 2 3 How to Enter Program Mode 6 2 6 2 4 How to Exit Program Mode 6 2 6 2 5 Step Programming...

Page 5: ...mmable relay output provides additional annunciation for either alarm or dialer failed condition Three LEDs indicating AC power green status Trouble Silenced yellow and Dialer Failed yellow Four LEDs...

Page 6: ...d to be performed Please let us know if the manual does not meet your needs in any way 1 3 1 How to Use This Manual In this manual the following conventions are used Pages of the manual are numbered b...

Page 7: ...number and then return it to Silent Knight 12 Clintonville Road Northford CT 06472 1610 800 328 0103 or 203 484 7161 If the Model 5104 causes harm to the telephone network the telephone company will n...

Page 8: ...d ensure that it is permissible for the equipment to be connected to the facilities of the local telecommunications company In some cases the company s inside wiring associated with a single line indi...

Page 9: ...rior walls below grade condensation Protect from plumbing leaks Protect from splash caused by sprinkler system inspection ports Do not mount in areas with humidity generating equipment such as dryers...

Page 10: ...stance as possible or use shielded cable Connect the shield to earth ground at the panel only High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be red...

Page 11: ...describes the 5104 board components including terminal strips LEDs Switches and cable connectors See Figure 3 2 Figure 3 2 5104 Circuit Board Terminal Block 1 Terminal Block 3 Terminal Block 2 P1 P2...

Page 12: ...Limited 0 7 Circuit Ground 0 8 Input Class B Style A Zone 3 0 9 Power Power Limited 0 10 Input Class B Style A Zone 4 0 11 Power Power Limited 0 12 Circuit Ground 0 2 13 Telco Ring Phone Line 1 N A 1...

Page 13: ...eans that any time the control panel dialer needs to communicate with the central station it will not be possible to use the tele phones that are on the same line as the fire system During communicati...

Page 14: ...devices depress the reset silence switch for a minimum of 1 second The Reset Silence switch is accessible inside the panel DO NOT install the switch extender provided with the system for UL certified...

Page 15: ...line A 3 Add up the current draw for all the smoke detectors and record the totals in line B 4 Total all the notification appliance device loads and enter that number into line C 5 Make sure that the...

Page 16: ...ubtotals mA mA Smoke Detectors Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA B Current Sub...

Page 17: ...quivalent material can be used to space the cabinet from the concrete surface and then attach the 5104B to that spacing surface Also mount any other desired components to the 1 4 spacing surface DO NO...

Page 18: ...d electrician Figure 3 4 AC Transformer Connections 3 9 Battery Connection The battery provides backup power to the system during AC power loss Connect the 12 VDC battery SK Model 6712 as shown in Fig...

Page 19: ...ected even after a single open or ground fault occurs When a single open or ground fault occurs the audible trouble signal will sound and the 5104 will report the trouble to the central station Figure...

Page 20: ...tation Figure 3 7 shows how to wire a class B style B loop One side of each class B loop connects to a zone input ter minal and the other side of each loop connects to loop power For each loop use a 4...

Page 21: ...e Detector Connection 4 wire smoke detectors must use a power supervision module Connect four wire smoke detectors as shown in Figure 3 8 Figure 3 8 4 wire Smoke Detector Connections Model 160150 Supe...

Page 22: ...Non Supervised Notification Appliance Wiring Figure 3 9 illustrates how to wire a non supervised notification device to the control panel Figure 3 9 Non Supervised Alarm Bell Wiring Note Polarities sh...

Page 23: ...w to wire a supervised notification device to the control panel Refer to Section 6 2 7 Step 14 to program the notification circuit s supervision properties Figure 3 10 Supervised Alarm Bell Wiring Not...

Page 24: ...o the phone lines with a 7860 cable which plugs into an RJ31X phone jack The telephone company will install an RJ31X phone jack if you request them Both telephone lines must be installed to comply wit...

Page 25: ...l box All wire runs must use 12 to 18 AWG wire with a maximum length of 1000 feet The annunciator must be supervised Follow these instruction to properly install the 5230 remote annunciator 1 Remove t...

Page 26: ...and snapping the 5230 into place Note Refer to Section 5 for 5230 Operation ID Number Dip Switch 1 Dip Switch 2 Dip Switch 3 Dip Switch 4 0 On On On On 1 Off On On On 2 On Off On On 3 Off Off On On 1...

Page 27: ...e 5104 as an add on communicator wire it as shown in Figure 4 1 Figure 4 1 5104 Add on Communicator Configuration Using 5104 Transformer for Power Note If power is supplied by the 5104 transformer the...

Page 28: ...ion exist on the zone or zones indicated by Low AC AC power has been lost Trouble Line 1 Trouble condition on phone line 1 Trouble Line 2 Trouble condition on phone line 2 Dialer Trouble Indicates a d...

Page 29: ...chpad Keystrokes and Their Task or Function Task or Function Keystroke Enter function or data Used initiate any command or to enter a step parameter into programming memory See examples below Enter Pr...

Page 30: ...to a remote computer Installer Code Display Troubles Used to display any system troubles Installer or Operator Code Display Memory Used to display all system events including Alarms Troubles and Supe...

Page 31: ...des 6 2 2 How to Enter and Exit Program Mode This section describes how to enter and exit programming mode 6 2 3 How to Enter Program Mode Follow these steps to enter program mode NOTICE TO USERS INST...

Page 32: ...Figure 6 1 Example of 5230 Display To enter a new value into line 2 simple enter that value and press the enter key Yes or No Selections When the selection choices are Yes or No you can press any numb...

Page 33: ...etting of those steps Table 6 2 Special Characters for Dialing Sequence Character Touchpad Inputs Displayed Character Pause A B C Look for second dial tone D Table 6 3 List of Programming Steps Step T...

Page 34: ...the setting between Yes or No Step 10 Line 2 Prefix 1 to 8 digits None Enter 8 digits to phone line 2 Use special characters to add pauses and look for second dial tone characters into the line 2 pre...

Page 35: ...d Trouble 1 Yes or No Yes Set priority for trouble reports Yes Priority phone number is 1 No Priority phone number is 2 Step 18 Send Test 1 Yes or No Yes Set priority for manual and auto test reports...

Page 36: ...a sprinkler Supervisory when using SIA format No If you want troubles and alarms to report as fires Alarm Note Bells will only sound if No is select ed Step 24 Report Sprnk 6 Yes or No No Set how zon...

Page 37: ...particular long distance carrier Use special characters to add pauses and look for second dial tone characters into the phone number See Table 6 2 for special characters Step 30 Phone 1 1 to 16 digit...

Page 38: ...tion other than 0 3 will scroll through the available selections Step 40 Zone Response 2 1 See Step 39 Step 41 Zone Response 3 1 Step 42 Zone Response 4 1 Step 43 Zone Response 5 1 Step 44 Zone Respon...

Page 39: ...ric digit to toggle the selection from Yes to No Yes If the 5104 is used as an add on communicator for a host panel This tells the 5104 not to test the battery or earth ground which could cause interf...

Page 40: ...1400 Hz See Table 6 1 3 1 23 Old format transmits a 3 digit account number and a 1 digit alarm code Transmissions are acknowledged at 2300 Hz See Table 6 1 4 2 SK 4 2 Tone burst format transmits a 4 d...

Page 41: ...rouble Code F1 F6 1 203 001 1 203 006 Sprinkler Trouble Restore 1 6 SJ1 SJ6 71 76 Restore Code E1 E6 3 203 001 3 203 006 Annunciator Trouble 1 3 ET1 ET3 33 Trouble Code FD 1 330 001 1 330 003 Annuncia...

Page 42: ...store Code EB 3 351 000 Communications Failure Line 2 YC2 32 Trouble Code FC 1 352 000 Communications Restore Line 2 YK2 36 Restore Code EC 3 352 000 Manual Test RX0 30 Test Code EE 1 601 000 Automati...

Page 43: ...uble condition on line 2 L5 On Dialer Trouble Indicates a dialer failed condition Earth Ground Fault Indicates that an earth ground fault condition exists Earth Pwr Fault Indicates that an earth power...

Page 44: ...Flashes Trouble Com 2 Event reports auto test or manual test unable to report on line 2 Phone line voltage is O K but the panel was unable to communicate on line 2 Try dialing the phone number that y...

Page 45: ...oard only Products that are returned in cabinets will be charged an additional 50 to cover the extra shipping and handling costs over board only returns Do not return batteries Silent Knight has the a...

Page 46: ...S EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY...

Page 47: ......

Page 48: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com...

Reviews: