15
User Guide DP300E
7OA0001 GB rev.09
Service Bypass Switch
EMERGENCY (UPS not alive)
1.
Turn the input switches (Q001) to position „0“.
2.
Turn the output switches (Q002) to position „0“.
3.
Turn the output isolator (Q004) to position “0”.
4.
Change possible released system input fuse(s).
5.
Turn the bypass switch (Q003) to position „1“.