Terminal Connections

Input

1

Transducer supply (+)
or optional Second Input (+)

2

Input Signal (+)

3

Input Signal Common (–)

Channel A

4

SPCO Normally Closed

5

SPCO Common

6

SPCO Normally Open

7

SP Common

8

SP Normally Open

Channel B

9

SP Normally Open

10 SP Common
11 SPCO Normally Open
12 SPCO Common
13 SPCO Normally Closed

Supply

14 Earth
15 Neutral
16 Line

Operation

The output relays of the dual trip amplifier
change state when the input signal
passes the points set on the front panel
mounted ‘Trip Point’ controls.

Single Input

The unit is normally connected internally
to be driven from one input signal.
Current input types are calibrated with a
signal input conditioning resistor which is
installed between terminals 2 and 3
(Input ‘A’ position) in the base section of
the module.

Please note

On early releases of this unit, the transducer
supply is not available. These units are
identified by “112-2A-080” on the PCB
adjacent to hysteresis pots.

Two Input Option

Where two separate inputs are specified,
the transducer supply is not available but
is replaced by a connection for a second
input signal. Each ‘channel’ is calibrated
to its respective input signal. Channel A
input signal connects to Terminal 1.

Current Inputs

For current inputs, when the plug-in
module is removed, signal loops are
maintained via a shunt resistor mounted
in the base section of the module. The
unit and its shunt resistor(s) are calibrated
as a matched pair. An error of

£

± 0.1%

can be expected if the instrument is used
with an unmatched input resistor (e.g. by
swapping plug-in modules.).

Front Panel Controls

The front panel controls are scaled
0-100% of the full scale input signal. The
LED indicators illuminate when the
respective relays are energised.

Transducer Supply

(i) Two wire transmitter connections

(ii) Three wire transmitter connections

DC versions only
Earth
Negative (–)
Positive (+)

[+]

[–]

2-wire transducer

[1]

[2]

[Power (+)]

[Ground]

3-wire transducer

[2]

[1]

[3]

[Signal]

Summary of Contents for 112-2A-2

Page 1: ...DUAL TRIP AMPLIFIER Type 112 2A 2 User Guide Document Ref UD112 2A 2 vp Rev 1...

Page 2: ...ood instrumentation practice must be observed when wiring to the unit to ensure segregation of supply and signal wiring and the use of suitably screened signal cabling WARNING This unit can be mains p...

Page 3: ...le These units are identified by 112 2A 080 on the PCB adjacent to hysteresis pots Two Input Option Where two separate inputs are specified the transducer supply is not available but is replaced by a...

Page 4: ...ug in module into the base section and secure with the retaining screws NB do not over tighten Internal Controls and Links Interlocked Output This mode is enabled by LK5 see Fig 1 Two modes of interlo...

Page 5: ...ck Enabled 240v link 2 3 4 5 220v link 2 5 110v link 2 6 1 5 sleeved Mains Supply Transformer or DC Power Unit AC Supply 100mA quick blow DC Supply 250mA anti surge Fuse Set Channel B Hysteresis Set C...

Page 6: ...ched when it would switch off The pump would then remain switched off until the low trip point was reached Setting up To set up the unit to operate with an interlock triggered by a Low Level 1 Ensure...

Page 7: ...the unit to operate with an interlock triggered by a High Level 1 Ensure Link 5 is set correctly see page 4 2 Set SW A to Low L 3 Set SW B to High H The front panel controls function as follows For th...

Page 8: ...tering is incorporated to reject RF and other industrial noise Supply Voltage Rejection Span change 0 01 span supply change Series Mode AC Rejection A hysteresis setting of 1 will reject 50 60Hz serie...

Reviews: