 — VMZ.2 

Installation of VMZ.2  

Technical changes reserved 

 

- 9 - 

 

 

  Installation can occur in horizontal and vertical pipes. The flow sensor is only suitable for 

application in completely filled pipe systems. 

  As a matter of principle magnetic inductive flow sensors are widely independent from the 

flow profile. An inlet section is not absolutely necessary. 

To reach a most highly accuracy of the measurement, you should use straight inlet and 

outlet sections according to the nominal width (DN). The inlet section has to be at least 

10 x DN; the outlet section 5 x DN in order to achieve the specified accuracy. 

  The inlet and outlet sections and the gaskets must have the 

same or a slightly larger inside diameter than the measuring 

tube in order to achieve the specified accuracy. 

  If two or more VMZ.2 devices are used side by side, maintain 

a separation of at least 2.5 cm between adjacent devices. 

If adjacent devices are too close together, operation of both 

devices may be impaired due to mutual interference.  

 
 

4.2  Assembly 

The VMZ.2 is installed directly into the pipeline. The compact design and light weight of the 

unit make wall-mounting unnecessary. 

 

IMPORTANT NOTICES: 

• Only use suitable gaskets for installation. 

• Observe the flow direction indicated on the type plate.  

• Observe the mounting dimensions (

 § 9.3 “Dimensions”). 

 

  Select an appropriate location for installation 

(

 § 4.1 “Installation instructions”).  

To ensure the best possible measuring accuracy, a vertical 

installation position with increasing flow is preferable (no col-

lecting of dirt deposits). 

  Install the appropriate screwed connections at the installation 

location.  

  Insert the VMZ.2 together with the gaskets. 

  Screw the union nuts of the screwed connection onto the pro-

cess connections of the VMZ.2. 

 

 

CAUTION! Material damage!  

Maximum torque 5 Nm. 

While tightening, counter the VMZ.2 only by hand! 

If you use an open-end or a pipe wrench, the VMZ.2 can be 

damaged. 

 

 

  Tighten both union nuts with a maximum torque of 5 Nm.  

 

 

 

 

 

 

Summary of Contents for induQ VMZ.2 Series

Page 1: ...re reference If the device is resold please provide the operating manual along with it SIKA Ba_VMZ 2_en 08 2020 Magnetic Inductive Flow Sensor Series VMZ 2 Types VMZ03 VMZ06 VMZ08 VMZ15 VMZ20 VMZ25 Op...

Page 2: ...2 Switching on and off 12 6 3 Measuring operation 12 7 Maintenance and cleaning 13 7 1 Return shipment to the manufacturer 13 8 Disassembly and disposal 14 9 Technical data 15 9 1 Characteristics VMZ...

Page 3: ...UTION Risk of injury This sign indicates dangers that cause personal injuries that can lead to health defects or cause considerable damage to property CAUTION Electric current This sign indicates dang...

Page 4: ...been carefully checked for their operational reliability before shipment Immediately after receipt please check the outer packaging for damages or any signs of improper handling Report any possible d...

Page 5: ...ircumstances be exceeded Before installing the device check that the wetted materials of the device are compatible with the media being used 9 2 Materials table Measuring tube empty or partially fille...

Page 6: ...be aware of this operating manual and have access to it at all times The electrical connection should only be carried out by a fully qualified electrician General safety instructions In all work the...

Page 7: ...n the middle of the measuring tube between the earthing sleeves The VMZ 2 does not need any moving parts to make measurements The inside of the measuring tube is completely open allowing the fluid to...

Page 8: ...E TOOLS Use only suitable tools of the correct size 4 1 Installation instructions CAUTION Risk of malfunction due to external magnet ic fields Magnetic fields close to the device can cause malfunction...

Page 9: ...t devices If adjacent devices are too close together operation of both devices may be impaired due to mutual interference 4 2 Assembly The VMZ 2 is installed directly into the pipeline The compact des...

Page 10: ...ON Electric current The electrical connection should only be carried out by a fully qualified electrician De energize the electrical system before connecting the VMZ 2 Connection cable Suitable connec...

Page 11: ...e type plate Supply voltage VMZ 2 with frequency output Push Pull NPN Open Collector PNP Open Collector 1 Push Pull switching outputs of several VMZ 2 may not be connected in parallel 2 Recommendation...

Page 12: ...Switch on the supply voltage The green LED lights up The VMZ 2 is ready and goes into measuring mode 6 3 Measuring operation In the measuring mode the green LED flashes proportional to the measured fl...

Page 13: ...operating company WARNING Risk of injury due to insufficient cleaning The operating company is responsible for all damages and harm of any kind in particular physical injuries e g caustic burns or to...

Page 14: ...tate the equipment is depressurised and has cooled down Disassembly Remove the electrical connectors Remove the VMZ 2 using suitable tools Disposal Compliant with the Directives 2011 65 EU RoHS and 20...

Page 15: ...ristics Frequency output Pulse rate K Factor pulses l 10 000 4000 1000 400 200 80 Resolution ml pulse 0 1 0 25 1 0 2 5 5 0 12 5 Signal shape Square wave signal duty cycle 50 50 Push Pull NPN open coll...

Page 16: ...DN 15 DN 20 DN 25 Inner diameter 3 mm 8 x 2 mm 8 mm 14 mm 18 mm 25 mm Max working pressure at C 10 bar 20 C 8 bar 40 C 6 bar 60 C higher pressure ratings on request Process connection male thread G B...

Page 17: ...Dimensions VMZ 2 DN 3 DN 6 DN 8 DN 15 DN 20 VMZ06 Type L1 L2 D1 D2 VMZ03 85 13 G B 3 VMZ06 85 13 G B 8 x 2 VMZ08 85 13 G B 8 VMZ15 90 16 G B 14 VMZ20 90 16 G1 B 18 VMZ 2 DN 25 L1 58 M12x1 13 5 D2 89 3...

Page 18: ...VMZ 2 18 SIKA Ba_VMZ 2_en 08 2020 For your notes...

Page 19: ...VMZ 2 Technical changes reserved 19 For your notes...

Page 20: ...SIKA Ba_VMZ 2_en 08 2020 SIKA Dr Siebert K hn GmbH Co KG Struthweg 7 9 34260 Kaufungen Germany 49 5605 803 0 49 5605 803 555 info sika net www sika net...

Reviews: