Series MHE-RE

Moonlite LED™
High Output Emergency Light

Fig. 4. RECESSED MOUNT- WIRING

24 VDC

OUTPUT

CEILING

24 VDC

INPUT

BL

Y
B
R

BL

Y
B
R

  BL YB R

POLARIZED

LAMP

CONNECTOR

LAMP

ASSBY

TRIM PLATE

24 VDC

OUTPUT

24 VDC

INPUT

BL

BL

Y
B
R

BL

Y
B
R

YBR

CEILING

KEY

B= BLACK:COMMON: 12/24 VDC NEG -
Y= YELLOW: EXITS/CVRE: 12/24 VDC POS +
R= RED: EMERGENCY: 24VDC POS +
BL= BLUE: NORMAL ON LIGHTING (NOL): 24 VDC POS +

1. Route 24VDC IN/OUT wiring from CBS system into Housing. 
 
2. Connect wiring with standard wire nuts to the supplied wiring pigtail, as shown. For emergency lighting operation only, connect RED and 
BLACK; for normally ON/security lighting operation, connect RED, BLACK and BLUE. (YELLOW wire is passed through and not connected to 
this fixture). 

3. Connect lamp plug and install lamp assembly with (4) #8 screws. Attach Trim Plate with (2) color- matched #8-32 screws as shown.

4. Supply 24 VDC power from Central Battery System to check lamp operation.

220  VFW Avenue, Grasonville, MD 21638

TEL: (410) 827-8300   Fax:(410)827- 8866

[email protected]    www.signtexinc.com

Signtex  Inc

LIGHTING

WIRING FOR EM OPERATION ONLY

WIRING FOR EM & NORMAL ON OPERATION 

PIGTAIL 

(SUPPLIED)

PIGTAIL 

(SUPPLIED)

02.17.02