background image

CAUTION!

•   Remove power to unit before wiring 

input and output connections.

•   Follow instructions carefully to avoid 

personal injury.

Signet 8450-3 Pressure Transmitter

Contents

1. Installation
2. Speci

fi

 cations

3. Electrical Connections
4. Menu Functions

Pres1:  4.5 

psi

Pres2:  2.3 

psi

ENTER

Signet Pressure

Transmitter

Output -

System Pwr
Loop -

System Pwr
Loop +

2

1

4

3

Sensr Gnd

(SHIELD)

Sensr IN

(RED)

Sensr V+

(BLACK)

7

6

5

   8052

92 mm
(3.6 in.)

97 mm

(3.8 in.)

56 mm 
(2.2 in.)

41 mm 
(1.6 in.

)

Optional
Rear
Cover

SIDE VIEW
Field Mount

96 mm

(3.8 in.)

96 mm
(3.8 in.)

96 mm

(3.8 in.)

quick-clips

gasket

panel

terminals

mounting

bracket

latch

Panel Mount

SIDE VIEW

FRONT VIEW

Field Mount &

Panel Mount

Panel Mount
Installation Detail

107 mm (4.2 in.)

42 mm 

(1.7 in.)

65 mm 

(2.5 in.)

1. Installation

ProcessPro transmitters are available in two styles: panel mount and 

fi

 eld mount. The panel mount is supplied with the necessary 

hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The 3-8052 integral kit joins the sensor and instrument together into a single 
package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other 

fi

 eld installation options are included with the 3-8052 Integral kit or the 3-8050 

Universal kit.

1.1 Panel 

Installation 

1.  The panel mount transmitter is designed for installation using a ¼ DIN Punch. For manual panel cutout, an adhesive template is 

provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch.

2.  Place gasket on instrument, and install in panel.
3.  Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument.
4.  To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
Press quick-clips outward and remove.

3-8450.090-3  Rev. H   11/11   

English

*3-8450.090-3*

English

China RoHS (Go to www.gfsignet.com for details)

•  Update rate:   

100 ms

• Accuracy:   

±0.03 

mA

Open-collector output: 

Hi, Lo, Off, Programmable:

•  Optically isolated, 50 mA max. sink, 30 VDC max. pull-up 

voltage

• Hysteresis:   

User 

adjustable

Environmental

•  Operating temperature:  -10 to 70 °C (14 to 158 °F) 
•  Storage temperature: 

-15 to 80 °C (5 to 176 °F)

•  Relative humidity: 

0 to 95%, non-condensing

•  Maximum altitude: 

2000 m (6562 ft)

• Insulation 

category: 

II

•  Rating: 

NEMA 4X/IP65 front

Standards and Approvals

•  CE, UL listed
• Immunity:  EN50082-2
•  Emissions: 

EN55011 Class B

•  Manufactured under ISO 9001 for Quality and

ISO 14001 for Environmental Management

2. Specifi cations

General

Compatibility: Signet 2450 Pressure Sensor
Accuracy:  ±1% of full scale
Enclosure:
• Case: 

PBT

•  Panel case gasket:  Neoprene
•  Window: 

Polyurethane coated polycarbonate

•  Keypad: 

Sealed 4-key silicone rubber

•  Weight: 

Approx. 325 g (12 oz.)

Display:
•  Alphanumeric 

2 x 16 LCD

•  Update rate: 

1 second

•  Contrast: 

User selected, 5 levels

Electrical

Power: 

12 to 24 VDC ±10%, regulated,

 

60 mA max current

Sensor Input:
•  Range: 

0-250 psig, 0-17 bar, 0-1700 kPa

Current output:
•  4 to 20 mA, isolated, fully adjustable and reversible
•  Max loop impedance: 

  50 

Ω

 max. @ 12 V,

 

   

325 

Ω

 max. @ 18 V,

 

   

600 

Ω

 max. @ 24 V

Summary of Contents for 8450-3

Page 1: ...al panel cutout an adhesive template is provided as an installation guide Recommended clearance on all sides between instruments is 1 inch 2 Place gasket on instrument and install in panel 3 Slide mounting bracket over back of instrument until quick clips snap into latches on side of instrument 4 To remove secure instrument temporarily with tape from front or grip from rear of instrument DO NOT RE...

Page 2: ...es two sensors the total length of cable connected to the transmitter is limited to 400 ft The 3 conductors from a dual sensor system can be tied together and then a single set of wires continued on to the transmitter For best performance ground the sensor SHIELD wire to a local earth ground at a point near the sensor Experiment with connecting the sensor shield wire to different local ground poin...

Page 3: ...r supply Internal PLC Connection Connection to a PLC Recorder separate supply PLC or Recorder Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Transmitter Terminals Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Transmitter Terminals Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Power Supply 12 24 VDC PLC Terminals Cha...

Page 4: ... variable moves below the setpoint plus the hysteresis value Hysteresis Time Low Setpoint Process Output energized Output de energized Hysteresis Time High Setpoint Process VIEW menu During normal operation the ProcessPro displays the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no activity occurs for 10 minutes To select the item you want disp...

Page 5: ...diting Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element w...

Page 6: ... 20 mA output Pressure 1 Pressure 2 or Delta Pressure Pressure1 Pressure2 Loop 1 Range psi 0 0 100 0 Check the 2450 Sensor instructions for the range capability of your sensor Be sure to modify this setting if you change the Pressure Units Output 1 Source Pressure1 Select the INPUT SIGNAL represented by this Open Collector Output Pressure 1 Pressure 2 or the Delta Pressure Pressure1 Pressure2 Outp...

Page 7: ...le display and output response Select LOW HIGH or OFF Output1 Active Low Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used to turn a device OFF at the setpoint Output2 Active Low Loop1 Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represe...

Page 8: ...641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece Display Condition Possible Causes Suggested Solutions Check Sensor Sensor not wired properly Sensor con...