background image

2

Signet 8450-2 Pressure Transmitter

3. Electrical 

Connections

Caution:

 Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure
  1.  Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire end.
  2.  Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
  3.  Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.
    The terminals will accomodate conductors from 14 to 22 AWG.
  4.  Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure
  1.  Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
  2.  When fully open, remove wire from terminal.

Wiring Tips:

•  Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal.
•  Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage.
•  Seal cable entry points to prevent moisture damage.
•  Only one wire should be inserted into a terminal. Splice double wires outside the terminal. 
•  The cable length from the sensor to the transmitter must not exceed 400 ft. (122 m)
•  For best performance, ground the sensor SHIELD wire to a local earth ground at a point near the sensor.
 

(Experiment with connecting the sensor shield wire to different local ground points to identify best signal quality.)

2
1

 

13 

12 

11 

 

 

10 

System Pwr 

Loop - 

 

System Pwr 

Loop + 

 

AUX 

Power -  

 

AUX 

Power + 

Sensr Gnd

(WHITE)

Sensr IN

(RED)

Sensr V+

(BLACK)

Relay 2

(NO)

Relay 2

(COM)

Relay 2

(NC)

Relay 1

(NO)

Relay 1

(COM)

Relay 1

(NC)

Terminals 5-10: Relay Outputs

Two sets mechanical SPDT contacts, programmable 
(see CALIBRATE menu) as:
 

• High or Low setpoint with adjustable hysteresis

 

• Proportional pulse output

 

• May be disabled (Off) if not used.

Terminals 3 and 4: Loop Power

12-24 VDC ±10% system power 

and current loop output.

•  Maximum loop impedance:

  50

Ω

 max. at 12 V

325

Ω

 max. at 18 V

600

Ω

 max. at 24V

Terminals 11-13: Digital sensor input

See next page for more information.

Terminals 1 and 2:  AUXILIARY power

Provides power for relay operation.

Summary of Contents for 8450-2

Page 1: ...is 1 inch 2 Place gasket on instrument and install in panel 3 Slide mounting bracket over back of instrument until quick clips snap into latches on side of instrument 4 To remove secure instrument temporarily with tape from front or grip from rear of instrument DO NOT RELEASE Press quick clips outward and remove 3 8450 090 2 Rev J 11 11 English 3 8450 090 2 English Signet Pressure Transmitter Pres...

Page 2: ...chanical damage Seal cable entry points to prevent moisture damage Only one wire should be inserted into a terminal Splice double wires outside the terminal The cable length from the sensor to the transmitter must not exceed 400 ft 122 m For best performance ground the sensor SHIELD wire to a local earth ground at a point near the sensor Experiment with connecting the sensor shield wire to differe...

Page 3: ...System Pwr Loop AUX Power AUX Power Loop Input 4 to 20 mA System Pwr Loop System Pwr Loop AUX Power AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power Example Two transmitters connected to PLC Recorder with separate power supply PLC or Recorder Transmitter 1 Terminals Transmitter 2 Terminals Power Supply 12 to 24 VDC Connection to a PLC with built in power supply Internal PLC Connection...

Page 4: ...utput The relay output can be used as a switch that responds when the process value moves above or below a setpoint Low Output energizes when process variable is less than the setpoint The output will be de energized when the process variable moves above the setpoint plus the hysteresis value High Output energizes when process variable is greater than the setpoint The output will be de energized w...

Page 5: ...edure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin f...

Page 6: ...y of your sensor Be sure to modify this setting if you change the Pressure Units Relay 1 Mode Low Select the desired mode of operation for the relay 1 output Options available are High or Low The signal may be disabled Off if not used Relay 1 Setpnt 10 0 psi In Low or High Mode the relay output 1 will be activated when the pressure reaches this value Be sure to modify this setting if you change th...

Page 7: ...se to changes in pressure Longer averaging period produces more stable display and output response Loop Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Loop Adjust 20 00 mA Test Loop Press UP or ...

Page 8: ...641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece Display Condition Possible Causes Suggested Solutions Check Sensor Sensor not wired properly Sensor con...

Reviews: