Document Reference: X-0036-01-07 Cadmus & Ratifi Operating Manual
Drawn: 13/11/2020
Page 44 of 66
1.20
Administrator Functions Not Already Covered Earlier.
1.20.1
Options
Once logged into the administrator screen, select a project, and then select “Options”
from the menu on the left.
Parameter Name
Description
Options
TEMPERATURE UNITS
Temperature units for screens, emails and reports.
Celsius, Fahrenheit and Kelvin
AUTOMATIC REPORT SETTINGS
REPORT DAY
Determines which day the weekly report is sent.
Days, Sunday to Saturday
(Default: Monday).
NEW REPORT TIME
Determines what time daily and weekly reports are sent.
Set time is HH:MM.
(Default 00:00 (Midnight))
LATE ALARM TRIGGER
LATE ALARM EMAIL REPETTION
LATE ALARM TRIGGER
Ratifi has an internal function which checks all devices connect at
regular intervals. If a device fails to connection within this period, it will
cause a “Late Alarm” to trigger and an email set to the administrator.
The default period is 120 minutes. The devices
connect every “UPLOAD
RATE” minutes. If a device is in NAP state, it will connect every 90
minutes.
When a device “UPLOAD RATE” is configured to 120 minutes or more.
The administrator should increase the “LATE ALARM TRIGGER” period to
be greater than the upload rate.
30 to 2880 minutes.
(Default: 120 minutes)
LATE ALARM EMAIL REPETITION
Once a late alarm is triggered, this setting determines how often the
Administrator is emailed a reminder that the alarm condition is still
present.
1 to 24 Hours.
(Default: 12 hours. If the alarm is not cleared a reminder will be
emailed every 12 hours).