Technical Data
4.1
Performance Data
Interfaces
1x VARAN In (Tyco Mini I/O)
4x VARAN Out (Tyco Mini I/O), +24 V switchable over VARAN,
500 mA per port
(therefrom, optional 1x Ethernet (Vte) or real-time Ethernet)
(maximum cable length: 100 m)
4.2
Electrical Requirements
Supply voltage
+18-30 V DC
UL: Class 2 or LVLC
(1)
Current consumption of +24 V
power supply
typically 0.25 A internal electronics supply
VARAN Out port load (maximum 2 A)
(1)
Limited Voltage/Limited Current
(1)
The device must be connected to a secondary galvanically separated
supply with a rated voltage of 24 V DC. In compliance with UL 249, max. 4
A, the fuse must be connected in the area between the supply source and
the end device.