SDI 101
S-DIAS SAFETY DIGITAL INPUT MODULE
Page 20
02.12.2019
5.1
Status LEDs
Bus Status
green
ON
bus communication OK
OFF
no supply available
BLINKING (5 Hz)
no communication
Safety-Used
yellow
ON
module is used and no error
OFF
module is not used or not in operational mode
Input Status
green
ON
input ON
OFF
input OFF
5.2
Applicable Connectors
Connectors:
X1-X5:
Connectors with spring terminals (included in delivery)
The spring terminals are suitable connecting ultrasonically compacted (ultrasonically
welded) strands.
Connections:
Stripping length/Sleeve length:
10 mm
Plug-in direction:
parallel to conductor axis or to PCB
Conductor cross section, rigid:
0.2-1.5 mm
2
Conductor cross section, flexible:
0.2-1.5 mm
2
Conductor cross section, ultrasonically compacted:
0.2-1.5 mm
2
Conductor cross section AWG/kcmil:
24-16
Conductor cross section flexible, with ferrule without plastic
sleeve:
0.25-1.5 mm
2
Conductor cross section flexible, with ferrule with plastic sleeve:
0.25-0.75 mm
2
(ground for reducing d2 of the
ferrule)