SCP 211
S-DIAS SAFETY CPU-MODULE
Page 32
11.10.2021
9
Mounting
The S-DIAS modules are designed for installation into the control cabinet. To mount the
modules, a DIN-rail is required. The DIN rail must establish a conductive connection with the
back wall of the control cabinet. The individual S-DIAS modules are mounted on the DIN rail
as a block and secured with latches. The modules must be mounted horizontally (module
label up) with sufficient clearance between the ventilation slots of the S-DIAS module blocks
and nearby components and/or the control cabinet wall. This is necessary for optimal cooling
and air circulation to ensure proper function up to the maximum operating temperature.
Recommended minimum distances between the S-DIAS modules and the surrounding
components or control cabinet wall: