S-DIAS SAFETY CPU-MODULE
SCP 111-2
08.09.2022
Page 37
12.2 Safety
SafetyState
State
Status of the Safety module.
_ModuleNotFound
The module was not found at the set position.
_SafetyClassOK
The module was located and initialized
without error.
_MemAllocFailed
An attempt to allocate memory for the module
has failed.
_ReadFWVerFailed
The module's firmware could not be read.
_ReinitConfig
The configuration in the CPU has changed
and the hardware classes are now being
updated.
_ModFromCfgNotFound
A module from the configuration is not
physically available, its hardware class has
been placed, however.
A module from the configuration is not
physically available and its hardware class
has not been placed.
A module from the configuration is not a C-
DIAS module (according to its HW path).
_UnsafeVarNotFound
An unsafe variable cannot be found in the
project.
Compare
the
syntax
in
the
SafetyDesigner and the project.
_UnknownCfgError
An error has occurred while reading the
configuration or when creating the routing
tables.
_AsyncComError
Several sequential asynchronous commands
failed. Please contact Sigmatek support
_DOsIncreasedRestartAp
p
The number or sized of the module access
was increased with a new Safety project. =>
The application must be restarted, because
the new data is not covered by the current
access.
_LostPowerSupply
The CPU supply has failed.
_WrongSafetyHW
The placed Safety modules in the project do
not match the actual modules.
For each physical module, a Safety object
must be placed in the project.
Run State
State
Shows whether the module is in operational mode.
0
operational mode inactive
1
Operational or temporary operational mode active
Service Mode
State
Shows the operating status of the module.
0
Operational Mode
1
Service Mode
2
"Check Configuration" Phase active
Error State
State
Shows whether the module has detected an error.
0
No errors detected
1
Error detected, time out during data exchange required by
another module.