4.2
Digital Inputs
Number
8
Input voltage
typ24 V
m30 V
Signal level
low: < +4.5 V
high: > +14 V
Switching threshold
typ11 V
Input current
typically 5 mA at +24 V
Input delay
typically 5 ms
4.3
Digital Outputs
Number
8
Short-circuit proof
yes
Maximum permissible continuous
load current/channel
0.5 A
Maximum total current
(all 8 channels)
2 A (100 % of on time)
Voltage drop over power supply
(output active)
1 V
Residual current output
(off)
12 µA
Turn-on delay
< 400
s
Turn-off delay
< 400
s
Max. braking energy of inductive
loads
1 channel 0.12 [Joules]