Sigma K1000 Series Operation & Maintenance Manual Download Page 4

Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual

3.1 Enable Controls

No Controls are enabled unless the enable controls key is inserted.  While the enable
controls key is inserted the  buzzer will beep every few seconds.

3.2 Silence Alarm Switch

To silence an alarm activated by operation of a detection zone, press the silence alarm
button. The alarm silenced indicator will  illuminate and the sounders will stop.
To mute the fault buzzer, press the silence alarm switch. The fault buzzer will now beep
every few seconds.

3.3 Reset & Lamp Test Switch

All Indicators may be illuminated, for testing purposes, by pressing the reset and lamp
test switch. If any Zones are in fire condition, these will  reset provided that the silence
alarms switch has first been operated and the input signal e.g. Break glass unit has
been restored to normal.

3.4 Evacuate Switch

Press the evacuate switch  to operate the Sounder Circuits. The Common Fire indicator
will be illuminated and the buzzer  will sound the alarm tone.

FRONT PANEL CONTROLS

2.7 This equipment is designed to be powered from the 220 - 240V C mains supply. The

mains connection must include a protective Earth conductor to the requirements of
BS:7671 (see annex 2).

2.8  The mains supply must be from a separate dedicated fused spur labelled "FIRE

ALARMS DO NOT SWITCH OFF".

2.9 The installation should be carried out by or under the   supervision of a competent

person and in accordance with the requirements of BS:7671:1992 requirements for
electrical installation, BS:5839: Part 1:1988 fire detection and alarm systems for buildings.

2.10 Connection of the 24V battery supply should be carried out with great care and respect.

Misconnection or  short circuiting of the battery terminals will result in FIRE.

2.11 The system fuse F2 should only be replaced with mains and battery disconnected.

Page 3 of 10

INSTALLATION - 

Continued

FRONT PANEL INDICATIONS

4.1 Supply Healthy Indicator

Under normal conditions only the green supply healthy indicator is illuminated. The
system healthy indicator will extinguish in the event of:-

(1)

Mains Failure

(2)

Battery Disconnection.

(3)

System Fuse Failure

(4)

Total Power Failure

(5)

Battery Fuse Failure

Summary of Contents for K1000 Series

Page 1: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Man 1048 Issue 05 October 2009 ...

Page 2: ...ontrols Front Panel Indications 3 FrontPanelIndications continued 4 InternalIndicators 5 InternalControls 6 InternalControls continued TerminalFunctions 7 TerminalFunctions continued 8 Annexe TypicalwiringConnections UseOfAux 24VOutput 1 SigmaInstallation MainsSupplyConnection 2 Connections To Detectors Sounders 3 K1002 PCB Layout 1 2 Zone K1006 PCB Layout 4 6 Zone 4 ...

Page 3: ...o be operated from 220 240V AC mains supplies and is of class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation 1 4 Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe SAFETY Page 2 of 10 INSTALLATION 2 1 Remove the front panel by ...

Page 4: ...e buzzer will sound the alarm tone FRONT PANEL CONTROLS 2 7 This equipment is designed to be powered from the 220 240V C mains supply The mains connection must include a protective Earth conductor to the requirements of BS 7671 see annex 2 2 8 The mains supply must be from a separate dedicated fused spur labelled FIRE ALARMS DO NOT SWITCH OFF 2 9 The installation should be carried out by or under ...

Page 5: ...immediate attention Zone fault indicators will illuminate in the event of 1 Disconnection or severance of zone wiring 2 Short Circuit on zone wiring 3 Removal of a sensor from its base 4 Disconnection of the end of line monitor resistor or active end of line unit LCMU 4 5 Fire Indicators Upon detection of a fire the red zone fire alarm indicator will flash to give warning of the area zone in fire ...

Page 6: ...inate in the event of a open circuit on one of the sounder lines 5 3 Fuse Fault Indicator This indicator will illuminate in the event of A Auxiliary fuse failure B System fuse failure 5 4 Earth Fault Indicator This indicator will illuminate in the event of a positive or negative earth fault i e Field wiring connected to earth 5 5 Rem Fire Sig disabled indicator Thisindicator will illuminateintheev...

Page 7: ...S1 S2 These outputs will operate together upon activation of a smoke detection zone opera tion of the evacuate switch or the remote Alarm input Each sounder circuit is pro tected by a 500mA fuse 8 2 Both outputs are monitored against open and short circuit faults in the field wiring Any such faults are annunciated by the front panel system fault indicator immediately 8 5 The sounder circuit is nor...

Page 8: ...ound 2 second on 2 second off This will pulse the Sounders at this rate if connected to the remote alarm input If continuous sounders Evacuate is required then link R143shouldberemoved as indicated on annex 3 Auxiliary 24V Output Max O P Current 100mA 12 1 The auxiliary 24V output is provided to power any additional equipment which is fitted to the system such as remote shutdown relays This output...

Page 9: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 8 of 10 ANNEXE 2 ...

Page 10: ...oring wiring Standard bases are used Removal of a detector indicates fault but detectors beyond the removed one will be inoperative Line continuity unit wiring Diode bases are used Removal of a detector indicates fault and detectors beyond the removed one remain operative Connections to sounders Page 9 of 10 ...

Page 11: ...es 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 10 of 10 ANNEXE 4 K1006 PCB layout 4 6 zone Sigma fuse option resistor locations K1002 PCB layout 1 2 zone Sigma fuse option resistor locations ...

Reviews: