www.sigineer.com
30
protected from over current of the AC input. The recommended specification of the AC breaker is 40A for
4KW~6KW, 80A for 8KW~12KW.
When in AC mode the AC input power will supply both the loads and AC charger, a heavier wire gauge for
AC Input is required. Please consult a qualified electrician about the specific wire gauge required.
There are 3 different ways of connecting AC input and output to the terminal block depending on the model.
Call our tech support if you are not sure about how to wire any part of your inverter.
Wiring Option 1
230V single phase
Input: Hot line+Ground
Output: Hot line+Ground
Wiring Option 2
240V split phase
Input: Hot line+ Hot line +Ground
Output: Hot line+ Hot line +Neutral
Note:
As the two split phase hot lines is 180 degrees out of phase with each other, the inverter is only able to
output full power at 240Vac.
Users can only get 50% nominal power from each one of the 120Vac hot lines of the split phase
inverter.
The biggest 120V single load the inverter can drive is 50% of its nominal power.
Don't loosen the inside screws holding the internal cables !
Damage caused by loosening inside screws is not covered under warranty!