8
8
3
2
device ID
hex
Read
Product ID
10
A
3
4
device PAC
hex
Read
Product PAC
14
E
3
1
sen_type
1-255
uint16
Read
Sensor or
Input Type
15
F
3
1
batt level
0-3
uint16
Read
Battery
level
16
10
3
1
err_status
0-1
uint16
Read
Sensor
error code
17
11
3
1
prm1
alm_status
0-2
uint16
Read
Alarm
status of
1st
parameter
18
12
3
1
prm2
alm_status
0-2
uint16
Read
Alarm
status of
1st
parameter
19
13
3
2
prm1 value
float
Read
1st
calculated
value
21
15
3
2
prm2 value
float
Read
2nd
calculated
value
23
17
3
1
batt %
10%, 30%,
60%, 99%
uint16
Read
Battery %
24
18
3
2
batt volt
0-3.67 vdc
float
Read
Battery
Voltage
26
1A
3
2
temp
oC
float
Read
RF module
temperature
28
1C
3
1
vref
0-3.67 vdc
uint16
Read
Vref of RF
Module
29
1D
3
1
btn1 status
0-1
uint16
Read
Button
status, 0:
released, 1:
pressed
30
1E
3
1
btn2 status
0-1
uint16
Read
Reedswitch
status, 0:
opened, 1:
closed
Here is the table for Configuration:
Modbus
Register
(Decimal)
Modbus
Register
(Hex)
Function
Code
(Read)
Function
Code
(Write)
# of
Registers
Description
Range
Default
Format
Property
Comment
256
100
3
16
1
modbus
address
1-247
1
uint16
Read/
Write
Modbus
address of
device
270
10E
3
16
1
Radio
Configuration 1-6
4
uint16
Read/
Write
RC zones
selection
1..6 is
RCZ1 ..
RCZ6
271
10F
3
16
1
tx_power
20
int16
Read/
Write
RF Tx
power
272
110
3
16
1
tx_repeat
0-1
1
uint16
Read/
Write
Number of
repeat, 0:
1 time, 1:
3 repeats