This address is used to set the System type.
Write one of the following value to this address.
2
= 3 Phase 3 Wire
3
= 3 Phase 4 Wire.
Writing any other value will return error .
40011
System
Type
40013
Pulse Width
of Relay
This address is used to set
of the Pulse output.
Write one of the following values to this address:
60
:
60 ms
100
:
100 ms
200
:
200 ms
Writing any other value will return error .
pulse width
40015
Reset Energy
Counter
This address is used to reset the Energy Counter.
Write zero value to this register to reset the energy counter.
Writing any other value will return an error.
40017
-
-
40019
Rs485 Set-up
Code
This address is used to set the baud rate, Parity, Number of
stop bits. Refer to Table 6 for details.
40021
Node
Address
This register address is used to set Device address
between 1 to 247 .
40023
Pulse Divisor
This address is used to set
of the Pulse output.
Write one of the following values to this address:
1
:
Divisor 1
10
:
Divisor 10
100
:
Divisor 100
1000
:
Divisor 1000 & in KWh and MWh divisor will be 1 by default.
Writing any other value will return an error.
pulse divisor
Address
Parameter
Description
40