Sierra INNOVA-SWITCH 215 Instruction Manual Download Page 26

IM-215 Rev-A.1                                                    Series Innova-Switch™                                             Page 26 of 42 

                    

following procedure can be used to verify preliminary operation. 

 

1.   Remove the instrument enclosure cover by turning counter clockwise to expose 

the LS3200 Switch 

electronics. 

 

2.   Turn on power at its source. 

 

3.   Observe that either the red or green LED comes on. 

 

4.   If neither lamp illuminates refer to the trouble shooting Section, 6.2. 

 

5.2 

L.E.D. and Relay Status Logic (Fail-Safe) 

 
5.2.1 

The L.E.D.s (Red and Green) are an indication of the sensors status (ie. dry or wet) 
and are not affected by the position of the fail-safe jumper J-2.  The fail-safe jumper J-
2 changes the relay activation status allowing the user to select the fail-safe power off 
condition most appropriate to the application.  Refer to the tables below that show the 
logic  conditions  between  the  sensors,  L.E.D.  lights,  relay  coil  and  contacts  for  each 
position of the fail-safe jumper J-2. 

 
5.2.2 

Normal Operation (as set at factory) 

 
 

The switch comes configured from the factory with the following operation with the J-2 
jumper in the B (2-3) position.  (Refer to Figure 8.0.) 

 

 

 

 

 

 

 

 

 

 

 

RELAY 

 

 

 

 

 

 

RED    GREEN   

RELAY   

CONTACT 

 

SENSOR STATUS 

 

 

LED 

LED 

 

COIL STATUS 

STATUS 

 
 

Dry, or Lower Thermal   

 

 

 

 

 

 

    o NC 

 

   Dispersion Fluid  

 

 

ON 

OFF 

 

Activated 

(ie. hydrocarbons) 

 

 

 

 

 

 

 

    o NO 

 

    

 

Wet, or Higher Thermal  

 

 

 

 

 

    o NC 

 

   Dispersion Fluid  

 

 

OFF 

ON 

 

Deactivated 

 

 

 

  (ie. water) 

 

 

 

 

 

 

 

 

    o NO 

    

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
5.2.3 

Alternate Operation (Field Selectable) 

 
 

The relay logic may be reversed by moving the J-2 jumper to position A(1-2).  (Refer 
to Figure 8.0.) 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY 

 

 

 

 

 

 

RED    GREEN   

RELAY   

CONTACT 

 

SENSOR STATUS 

 

 

LED 

LED 

 

COIL STATUS 

STATUS 

 
 

 

 

 

 

 

 

 

 

 

   

   o NC 

 

Dry, or Lower Thermal   

 

ON 

OFF 

 

Deactivated 

Summary of Contents for INNOVA-SWITCH 215

Page 1: ...ers 5 Harris Court Building L Monterey California USA 93940 Toll Free 800 866 0200 USA only Phone 831 373 0200 Fax 831 373 4402 Website www sierrainstruments com Sierra Europe European Headquarters Bi...

Page 2: ...N SENSORS PERPENDICULAR TO THE FLOW BEING DETECTED DUE TO THE PIPE THREAD MOUNTING IT MAY BE NECESSARY TO MAKE A TRIAL FIT ADD OR REMOVE TEFLON TAPE OR OTHER PIPE THREAD SEALANT AND REINSTALL TO ACHIE...

Page 3: ...on the transformer configuration tag NOTICE This manual covers the following model numbers Innova Switch Series Models 215 FS4200 215 LS3200 Agency Approvals Explosion Proof rating Mass Flow Switch Po...

Page 4: ...ION FLOW 5 0 OPERATION AND CALIBRATION OF THE Innova Switch SWITCH FOR POINT LEVEL APPLICATIONS 5 1 PRE OPERATIONAL CHECKS 5 2 L E D AND RELAY STATUS LOGIC FAIL SAFE 5 3 CALIBRATION LEVEL 6 0 MAINTENA...

Page 5: ...erential created between the heated and reference RTD pair is a function of the density and or velocity of the media with which the sensor is in contact Other physical properties may have a secondary...

Page 6: ...IM 215 Rev A 1 Series Innova Switch Page 6 of 42 FIGURE 1A LS3200 FS4200 Innova Switch OUTLINE DIAGRAM STANDARD 2 0 INCH INSERTION KILLARK ENCLOSURE NEMA 4 EExd 11B T4...

Page 7: ...IM 215 Rev A 1 Series Innova Switch Page 7 of 42 FIGURE 1B LS3200 FS4200 Innova Switch OUTLINE DIAGRAM STANDARD 2 0 INCH INSERTION AKRON ELECTRIC ENCLOSURE NEMA 4X EexdIIC T4...

Page 8: ...two media the Innova Switch can discriminate between them Figure 2A shows the relative signal output of the Innova Switch sensor to a range of different media The maximum difference in output occurs...

Page 9: ...ure measurements of the fluid and finally combine density and volumetric flow to obtain mass flow The SIERRA INSTRUMENTS thermal differential technique is one of two methods that directly measure the...

Page 10: ...S Appendices in section 9 0 contain flow conversion information to facilitate conversion from various units and pipe dimensions into flow velocity in feet per second Gas Or Liquid Flow Note The fluid...

Page 11: ...IM 215 Rev A 1 Series Innova Switch Page 11 of 42 FIGURE 2B Innova Switch MODEL FS4200 FLOW RESPONSE FOR THREE MEDIA...

Page 12: ...the trip point is set by adjusting the Trip Adjust Potentiometer Solid state electronics transform the flow or wetting induced temperature differential into a voltage that is compared to a control vo...

Page 13: ...va Switch Page 13 of 42 Figure 3B shows a block diagram of the Innova Switch with the addition of an EMC filter required for the CE options see section 7 0 FIGURE 3B Innova Switch MODELS WITH THE CE O...

Page 14: ...o access the terminal block and facilitate field wiring see Figure 4 0 For applications where the electronics must be located away from the sensors due to elevated process temperature accessibility et...

Page 15: ...THE HEX FLATS OF THE MNPT OF A STANDARD SWITCH IF YOU HAVE A NON STANDARD SWITCH AN ALTERNATE SIZE WRENCH MAY BE REQUIRED DO NOT USE THE INSTRUMENT HEAD TO TIGHTEN THE SWITCH TO THE MOUNTING PORT ROTA...

Page 16: ...IM 215 Rev A 1 Series Innova Switch Page 16 of 42 FIGURE 5 PROPER ORIENTATION OF THE SENSOR PROBE FOR LEVEL AND FLOW APPLICATION IS INDICATED BY THE ARROW ON THE FLAT OF THE MOUNTING FITTING...

Page 17: ...ELECTRONICS FIELD WIRING DIAGRAM NOTES 1 Connections to sensors terminal block A TBA are factory installed and should not be disconnected in the field Note Jumpers 1 2 3 4 and 5 6 must be in place on...

Page 18: ...s marked on the transformer configuration tag and the serial number mounting wings or bracket provided Connect the switch wiring between the Innova Switch Switch remote electronics as shown in Figure...

Page 19: ...IM 215 Rev A 1 Series Innova Switch Page 19 of 42 FIGURE 7A Innova Switch FLOW SWITCH REMOTE ELECTRONICS OPTION FIELD WIRING...

Page 20: ...IM 215 Rev A 1 Series Innova Switch Page 20 of 42 FIGURE 7B REMOTE ELECTRONICS CABLE TERMINATION AND CONNECTIONS...

Page 21: ...rmer and pulling it straight out Connect power and alarm relay wiring to Terminal Block TBB as shown in Figures 6 0 and 6A Reinstall the Innova Switch Switch electronics and tighten the captive screws...

Page 22: ...Green are an indication of the sensors status ie flow below the setpoint or flow above the set point and are not affected by the position of the failsafe jumper J 2 The failsafe jumper J 2 changes the...

Page 23: ...ration Field Selectable The relay logic may be reversed by moving the J 2 jumper to position A 1 2 Refer to Figure 8 0 RELAY RED GREEN RELAY CONTACT SENSOR STATUS LED LED COIL STATUS STATUS o NC No Fl...

Page 24: ...15 Rev A 1 Series Innova Switch Page 24 of 42 FIGURE 9 0 Innova Switch FS4200 FLOW SWITCHCALIBRATION REFERENCE DRAWING 4 3 Calibration Flow IMPORTANT FOR OPTIMUM OPERATION CALIBRATION MUST BE ACCOMPLI...

Page 25: ...calibration 8 Set the trip adjust pot to 100 fully cw 9 Adjust the span adjust pot so that the Green LED just does illuminate This is a 25 turn pot If the Green LED is on turn the pot cw If the Red L...

Page 26: ...ower off condition most appropriate to the application Refer to the tables below that show the logic conditions between the sensors L E D lights relay coil and contacts for each position of the fail s...

Page 27: ...drocarbons o NC Wet or Higher Thermal OFF ON Activated Dispersion Fluid o NO ie water FIGURE 8 0 Innova Switch ELECTRONICS 5 3 Calibration Level IMPORTANT FOR OPTIMUM OPERATION CALIBRATION MUST BE ACC...

Page 28: ...G 5 3 Calibration Level Using Figure 10 0 as a location guide adjust the system as follows 1 Remove the instrument enclosure lid by turning ccw 2 Apply power to the unit Allow 5 minute warm up 3 For o...

Page 29: ...wet covered 9 Set the trip adjust pot to 100 fully cw 10 Adjust the span adjust pot so that the Green LED just does illuminate This is a 25 turn pot If the Green LED is on turn the pot cw If the Red...

Page 30: ...ds or unusual cleansers IMPORTANT DO NOT SANDBLAST OR ABRASIVE CLEAN THE SENSING PROBES THE SENSING PROBES COULD BE DAMAGED BY ABRASIVES 6 2 Troubleshooting 6 2 1 Power and Continuity Verification 1 T...

Page 31: ...ff to Innova Switch 2 Allow a 5 minute cool down 3 Measure the resistance of each RTD at pins 1 and 6 of TBA see Figure 6 0 or 7 0 for the hot RTD and pins 3 and 5 of TBA for the cold RTD These resist...

Page 32: ...osure EEx d IIB T4 Killark Enclosure CE EMC Directive 89 336 EEC CE Option OPERATING TEMPERATURE Process 70 C to 200 C 100 F to 390 F standard to 600 C 1000 F optional Electronics 40 C to 60 C 40 F to...

Page 33: ...cur during normal use LIMITS AND EXCLUSIONS SIERRA INSTRUMENTS SHALL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LOSS OF USE LOSS OF SALES OR INCONVENIENCE RESUL...

Page 34: ...182 Remote MT HT Options Fuses 101603 FS42 LS32 Wickmann 3740250041 101605 FS42 LS32 Cenelec Wickmann 3720250041 Manuals IM 4200 Innova Switch Manual Enclosures 101790 Standard Enclosure 101797 Standa...

Page 35: ...PM CFPS 1 667 E 02 Cubic In Per Minute CIPM CFPS 9 645 E 06 Milliliters Per Minute MLPM CFPS 5 886 E 07 Milliliters Per Second MLPS CFPS 3 531 E 05 Milliliters Per Hour MLPH CPFS 9 810 E 09 Liters Per...

Page 36: ...IM 215 Rev A 1 Series Innova Switch Page 36 of 42 9 2 FLOW CONVERSION CHART...

Page 37: ...IM 215 Rev A 1 Series Innova Switch Page 37 of 42 9 3 FLOW OF WATER THROUGH SCHEDULE 40 STEEL PIPE...

Page 38: ...IM 215 Rev A 1 Series Innova Switch Page 38 of 42 10 0 OPTIONS 10 1 LIVETAP LT...

Page 39: ...IM 215 Rev A 1 Series Innova Switch Page 39 of 42 10 2 VARIABLE INSERTION VI...

Page 40: ...IM 215 Rev A 1 Series Innova Switch Page 40 of 42 10 3 THERMOCOUPLE OUTPUT TO and 10 4 RTD OUTPUT RT...

Page 41: ...IM 215 Rev A 1 Series Innova Switch Page 41 of 42...

Reviews: