P1, P2, P3, P4: Input Supervision active / in-active
These headers select NAC input zone supervision being active or inactive. If
the usage application is set for speaker function, remove the shunt jumpers.
If the usage application is set for strobe place the two shunt jumpers of each
header between pins 1-3 and 4-6.
P1 selects NAC input supervision for Zone 1
P2 selects NAC input supervision for Zone 2
P3 selects NAC input supervision for Zone 3
P4 selects NAC input supervision for Zone 4
P5: Not used
No shunt jumpers set
J3: Not used
No shunt jumpers set
Output Zones
The ZIC-4AC can be configured for the following usages:
Speaker zone one or two channel
Strobe, Bell, Horn steady (Unsynchronized) and pulsing (Synchronized)
ZIC-4AC Switch and Jumper Settings
Zone Usage
S1
S2
Header Position
Speaker Zone
OFF (up)
OFF (left)
none
NAC
OFF (up)
OFF (left)
1-3 and 4-6
Programming Options
Each ZIC-4AC card is subdivided into four output circuits that can be
programmed independently of each other. In the
Zeus
Programming Tool,
highlight the selected ZIC-4AC Output Ckt in the
Physical View
and open the
Detail View
-
Properties
to modify and/or define the following ZIC-4AC
output circuit properties:
CAN Address
This address must match the
address set in the ZIC-4AC
hardware. (001 to 099)
Slot Location
This defines the location where
the ZIC-4AC is inserted in the
CC-5/CC2.
Base Language Custom Message
The message associated with the
ZIC-4AC output circuit.
Alternate Language Custom Message
The message associated with the
ZIC-4AC output circuit in an
alternate language.
Disarm at Startup
Determines if the ZIC-4AC
Output Ckt is disarmed after
initial power-up.
Degrade Alarm Activation
Determines if Degrade Alarm will
activate the ZIC-4AC circuit when
asserted.