OPERATION 

 

The XMS-S, XMS-D, and XMS-M manual stations operate with 
the Desigo Fire Safety Modular/Cerberus PRO Modular via the 
XDLC.  These devices can  be  wired  in  either Isolation  Mode  or 
Polarity  Insensitive  Mode  Wiring).  The  XMS-S/XMS-M  manual 
station front cover has a recess pocket to pull down and locks in 
position  after  the  alarm  is initiated.  The  XMS-D manual  station 
has  an  additional  lever  labeled  “PUSH  HERE  THEN”  to  get 
access to the front cover pocket to initiate the alarm. 

Resetting the Manual Station

 

To reset the stations, insert the Siemens T45 key provided into 
the key lock and turn the key 10-15 degrees counter-clockwise as 
the arrow shows. The cover will move upward to the normal 
position. Rotate the key clockwise and remove key from the lock. 
At 

Normal position

 the top of the Cover is flush with the top 

surface of the Base. Reset the Fire Alarm Control Panel to clear 
the alarm.

 

LED 

 

Diagnostic LED provides visible indication of the manual station 
status.   

Normal

: Green, LED flashes   

Alarm

: Red, LED flashes   

Trouble

:  Amber,  LED  flashes.  This  will  happen  when  the  Front 

Cover is removed from the Manual Station. 

NOTES: 

1.  Recommended wire sizes: 18 AWG minimum, 14 AWG 

maximum. 

2.  When using shielded cable with or without metal 

raceway, the shields must be grounded solely at the 
point of origin, for example, at the control panel. 

WIRING 

 

 

 

Figure 1   

Figure 2 
Isolator Mode Wiring   

 

Figure 3 
Polarity Insensitive Mode Wiring   

Single/Dual Action Manual Pull Stations   

The  Model  XMS-S  is  a  single  action  pull  station  in  a  plastic 
housing that requires one action by the user to initiate the alarm. 
The  Model  XMS-D  is  a  double  action  pull  station  in  a  plastic 
housing that requires two actions by the user to initiate an alarm. 
The  Model  XMS-M  is  a  single  action  pull  station  in  a  metal 
housing that requires one action by the user to initiate the alarm. 
These models are field installed addressable devices containing 
advanced  control  panel  communication  technology.  This 
technology, which provides two-direction communication with the 
control panel, produces an Intelligent Initiating Device. 

Programming Instructions 

 

Refer  to  Figure  1  to  locate  the  programming  holes  which  are 
accessible through the rear cover. 

CAUTION:

 To prevent potential damage to the DPU DO NOT 

connect  an  XMS  to  the  DPU  until  the  wire  at  terminal  1  is 
removed.  Follow  the  instructions  in  the  DPU  Manual,  P/N 
315-033260,  to  program  the  XMS  to  the  desired  address. 
Record the device address on the label and attach it to the top 
surface of the base. The XMS can now be installed and wired to 
the system as shown in Figures 2, 3, and 4. 

Programming Holes Location 

 

A6V11856080_enUS_a                               

 

 

Programming

Holes

Rear Cover

Line+

Line-

From control panel or
previous addressable device

To next addressable
device

Line-

Line+

Line 2

Line 1

From control panel or 
previous addressable 
device

To next addressable
device

Line 2

Line 1