Pin assignments for releasing module
X5 plug connection for releasing relay output
4
9 | 14
Building Technologies
A6V10315050_e_en_--
Siemens Industry, Inc.
2016-10-27
Class A wiring
Figure 4: Class A wiring
Note 1
Loop wires must be terminated directly onto the SOLENOID
Note 2
Loop wires must be terminated directly onto the SOLENOID
*REL-EOL: Terminating resistor 24 k
Ω
and diode (Siemens part number 500-696359)
The maximum length of line of the relay connections is limited to a resistance of 3.5
Ω
.
X5
4
3
2
1
+
+
-
-
REL_CIR1
REL_CIR1
REL_CIR2
REL_CIR2
*
REL-EOL
SOLENOID
.
x
.
x
Note 1
Note 2