Siemens WLTS Application Manual Download Page 4

4

Testing the tripping function

Long-time delayed tripping test

The long-time delay tripping function and the trip unit 
circuitry can be tested using the test device.

1.   Charge the circuit breaker

2.   Close the circuit breaker

3.   Press the [L] button

The circuit breaker will trip after the set long-time delay time, 
plus approximately two seconds processing time, has elapsed. 
When the test device successfully completes the test, the 
"ETU STATUS" LED will light up continuously green. If the test 
is not successful, the tester will indicate that by flashing the 
LED. Flashing codes are listed in Table 1.

Short-time delayed tripping test

The short-time delay tripping function and the trip unit 
circuitry can be tested using the test device.

1.   Charge the circuit breaker

2.   Close the circuit breaker

3.   Press the [S] button

The circuit breaker will trip after the set short-time delay 
time, plus approximately two seconds processing time, has 
elapsed. When the test device successfully completes the test, 
the "ETU STATUS" LED will light up continuously green. If the 
test is not successful, the tester will indicate that by flashing 
the LED. Flashing codes are listed in Table 1.

Instantaneous tripping test

The instantaneous tripping function and the trip unit circuitry 
can be tested using the test device.

1.   Charge the circuit breaker

2.   Close the circuit breaker

3.   Press the [I] button

The circuit breaker will trip after approximately two seconds 
processing has elapsed. When the test device successfully 
completes the test, the "ETU STATUS" LED will light up 
continuously green. If the test is not successful, the tester will 
indicate that by flashing the LED. Flashing codes are listed in 
Table 1.

Neutral conductor tripping test

The long-time delay tripping function for the neutral 
conductor and the trip unit circuitry for ETU types 727-776 
can be tested using the test device. The current sensor for the 
neutral conductor must be attached

 

and the "Neutral 

conductor protection" function must be switched on.

1.   Charge the circuit breaker

2.   Close the circuit breaker

3.   Press the [N] button

The circuit breaker will trip after the set long-time delay time 
plus approximately two seconds processing time, has elapsed. 
When the test device successfully completes the test, the "ETU 
STATUS" LED will light up continuously green. If the test is not 
successful, the tester will indicate that by flashing the LED.  
Flashing codes are listed in Table 1.

Ground-fault tripping test

The ground-fault tripping function and the trip unit circuitry 
of ETU types 745-746 with an installed ground-fault 
protection module (with tripping function WLGFM48 or 
WLGFM76) can be tested using the test device. The current 
sensor for the neutral conductor and/or the iron-core ground-
fault sensor must be attached.

1.   Charge the circuit breaker

2.   Close the circuit breaker

3.   Press the [G] button

The circuit breaker will trip after the set ground-fault tripping 
delay time, plus approximately two seconds processing time, 
has elapsed. When the test device successfully completes the 
test, the "ETU STATUS" LED will light up continuously green. If 
the test is not successful, the tester will indicate that by 
flashing the LED. Flashing codes are listed in Table 1.

DANGER

!

Hazardous Voltage.
Will cause death or serious injury.
Qualified personnel only.

Disconnect and lock off all power before 
working on this equipment.

 • Always work on de-energized 
    equipment.

 • Always de-energize before 
    performing any tests, maintenance,
    or repair.

 • Follow safety related work practices,
    as described in NFPA 70E, at all times.

NOTICE

Erroneous test results may occur when the trip 
unit is powered by either:

• Load current
• External 24 vdc control power

All testing should be conducted with the primary 
bus de-energized, and external 24 vdc control 
power disconnected or turned off.

DANGER

!

Hazardous Voltage.
Will cause death or serious injury.
Qualified personnel only.

Disconnect and lock off all power before 
working on this equipment.

 • Always work on de-energized 
    equipment.

 • Always de-energize before 
    performing any tests, maintenance,
    or repair.

 • Follow safety related work practices,
    as described in NFPA 70E, at all times.

NOTICE

Erroneous test results may occur when the trip 
unit is powered by either:

• Load current
• External 24 vdc control power

All testing should be conducted with the primary 
bus de-energized, and external 24 vdc control 
power disconnected or turned off.

Summary of Contents for WLTS

Page 1: ...WLTS Hand Held Test Set WL Low Voltage Circuit Breakers www usa siemens com WLBreaker Application Guide ...

Page 2: ... including the trip unit rating plug trip coil current sensors and all associated wiring The WLTS has additional functionality that is beneficial during startup and commissioning activities The WLTS can be utilized as a temporary power supply to provide control power for the WL family of trip units facilitating the programming of the trip unit during startup and commissioning The WLTS will supply ...

Page 3: ... any time by holding down the START button for three seconds Testing the current and energy sensors To test the current sensors and energy transducers press the START button A lit up LED confirms the proper operation of the corresponding sensor transducer If an LED flashes the corresponding sensor converter is not present not properly connected or is in need of replacement Whether a flashing N or ...

Page 4: ...e the circuit breaker 3 Press the N button The circuit breaker will trip after the set long time delay time plus approximately two seconds processing time has elapsed When the test device successfully completes the test the ETU STATUS LED will light up continuously green If the test is not successful the tester will indicate that by flashing the LED Flashing codes are listed in Table 1 Ground faul...

Page 5: ... communication interface to the connected CubicleBUS modules and the connected Modbus PROFIBUS DP networks Currents will be displayed on the trip unit only if the trip unit is equipped with an integrated display WLETU745 with WLLCD748 WLETU748 with WLLCD748 WLETU776 Current values will be available to be communicated when a communication interface is installed 1 Connect 24 V dc to power the trip u...

Page 6: ...ode Legend Arcing Contact Condition Alignment Primary Finger Clusters A Like New Condition Arc Chute Condition Frame Condition B Good Condition Open Close Indicator Breaker Cleanliness C Poor Condition Requires Correction Ready to Close Indicator Manual Close Trip D Corrections Made or Part Replaced Lubrication Electric Close Trip E Unacceptable Condition Do Not Use Mechanical Condition Manual Cha...

Page 7: ...7 Notes ...

Page 8: ... USA 2016 Siemens Industry Inc Subject to changes and errors The information given in this document only contains general descriptions and or performance features which may not always specifically reflect those described or which may undergo modification in the course of further development of the products The requested performance features are binding only when they are expressly agreed upon in t...

Reviews: