Figure 9. Example Results from the TEST Command.
Table 12 de
fi
nes TEST command result parameters.
Table 12. TEST Command Result Parameters.
Parameter
Indicates
For a TEST command result of
2340.591 1 12 0 1 -43 -41 -98
2340:591
Seconds since last WRS reset
1
Message sequence number
12
Message reponse time (in milliseconds)
0
Number of MAC backoffs
1
Number of message attempts
–43
WRS-to-RSX RSSI value
–41
RSX-to-WRS RSSI value
–98
Background RSSI value
Viewing All Data (INFO)
You can use the INFO command to get complete con
fi
guration, operational and communication status,
and diagnostic information from the WRS and RSX. The INFO command automatically executes the
following commands (one at a time in the order listed):
•
PARAM WRS
•
STATUS WRS
•
COMM WRS