Siemens VSA-1 Installation Instructions Download Page 4

Figure 4

VSA-1/VSM-1/VLM-1/VFM-1 Wiring Diagram

NOTES:

1. If only VSA-1 modules and no VSM-1, VLM-1, or VFM-1 modules are used in the

system, P2 of the first VSA-1 module is connected directly to TBM-2, P4, using the 3-

foot cable supplied with the TBM-2.

2. The custom annunciator manufacturer should use 12-position female connectors, such

as AMP No. 1-640440-2. Hood for connector is AMP No. 1-640550-2; key for connector

is AMP No. 641994-1. The hood and key are the same as those used for connection to

the MID-16 module. Two keys should be inserted at slots 1 and 12 of the female

connector, leaving 10 slots for connection to the VSA-1 header.

P/N 315-096072-4

Summary of Contents for VSA-1

Page 1: ...s All Call All Alarm EVAC Warden s Page and Local Speaker The switch use and zone groupings are assigned in CSG M The VSA 1 module may provide LED annuncia tion of system activity when the switch and LED pair are programmed as generic Each VSA 1 module contains 8 sets of 2 LEDs in three different colors to indicate a variety of system information such as zone trouble or alarm In each set the top L...

Page 2: ... 0 0 X X 0 0 28 0 X X X 0 0 13 0 0 X X 0 X 29 0 X X X 0 X 14 0 0 X X X 0 30 0 X X X X 0 15 0 0 X X X X 31 0 X X X X X NOTE To open a dipswitch press down on the side of the dip switch marked OPEN To close a dipswitch press down on the side of the dipswitch opposite the side marked OPEN To open a slide switch push the slide to the side opposite the side marked ON To close a slide switch push the sl...

Page 3: ... to P4 of the TBM 2 Termination Block module using the 3 foot cable supplied with the TBM 2 P N 600 192258 The cables are polarized do not force them NOTE The TBM 2 module is located in the enclosure on the right side next to the MMB 2 or the PSR 1 For more details refer to the MXLV Manual P N 315 092036 In a Remote Extender enclosure with a PS 5N7 used instead of an MMB or PSR Connect P2 of the f...

Page 4: ... supplied with the TBM 2 2 The custom annunciator manufacturer should use 12 position female connectors such as AMP No 1 640440 2 Hood for connector is AMP No 1 640550 2 key for connector is AMP No 641994 1 The hood and key are the same as those used for connection to the MID 16 module Two keys should be inserted at slots 1 and 12 of the female connector leaving 10 slots for connection to the VSA ...

Reviews: