19 – 6
19.1.5
Mechanical interlocking three sources (open transition to standby system)
The standby system is mechanically interlocked with the two source circuit breakers to prevent paralleling the standby system with either or
both primary source(s).
Description:
Two circuit breakers (S
1
, S
3
) can be independently opened and closed, the third (S
2
) being ready to close only if the other two are open. If
the third is closed, the other two cannot be closed.
Materials required:
Each circuit breaker has an interlocking module and a Bowden cable. A Bowden cable must be ordered separately.
Order no.
Connections of Bowden cables:
Example
Possible circuit breaker states
S
1
S
2
S
3
1st Bowden cable:
S
1
A
1
-
S
2
E
1
2nd Bowden cable:
S
2
A
1
-
S
1
E
1
3rd Bowden cable:
S
2
A
2
-
S
3
E
1
4th Bowden cable:
S
3
A
1
-
S
2
E
2
S
1
S
2
S
3
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......