5 – 6
5.3
Connecting the main conductors
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
Clean the main conductor connection
(plated busbars)
Securing line and load-side busbars
0058_u
Use grade 5 bolts
1
/
2
“ and Belleville washers. Tighten to a torque of 70 Nm / 50 lb-ft.