18/54
Siemens
TX-I/O™ Module system – Functions and operation
CM110561en_08
Building Technologies
Digital input functions
2018-10-25
The following events (telegrams) are used:
Event Description
Tg 1
Report on current status (for COV repetition)
Tg 2
Rising slope (start of short or long pulse)
Tg 3
Click completed
Tg 4
Start of a long pulse
Tg 5
Repeat, long pulse active
Tg 6
Long pulse completed
Tg 7
Start short double-click
Tg 8
Short double-click completed
Tg 9
Start short/long double-click
Tg 10
Start long double-click (two clicks with one long pulse at start)
Tg 11
Long double-click completed
Tg 12
Dual click (both buttons pressed simultaneously)
Tg 13
Dual click completed
Normally, preparameterized buttons are used that are customized for the blinds/lighting
applications to be used.
If individual parameterization is required, the function provides great flexibility to
implement any operating philosophy.
The following parameters are available:
Parameter
Description
Default
Source.Size
1 or 2 (simple/dual button)
1
tp
Pulse length
0.1...25.5 s
(increment 0.1 s)
0.5 s
tr
Repeat length
0.1...25.5 s
(increment 0.1 s)
1.0 s
td
Double-click length 0.1...25.5 s
(increment 0.1 s)
0.5 s
Enable Flags
If set
If not set
Default
Positive Edge Enable Rising slope sent
Rising slope not sent
Disabled
Stop Long Enable
Sends Tg 6 at the end of a long
pulse
Falling slope for long pulse
(Tg 6) not sent.
Disabled
Stop Long Double
Enable
Sends Tg 11 at the end of a long
double-click
Falling slope for long double-click (Tg
11) not setn
Disabled
Repeat Enable
Repeats Tg 5 with interval of tr
while button is pressed
Sends no Tg 5
Enabled
ShortDoubleClick
Enable
Sends Tg7, Tg8, Tg9, if short or
long/short double-click is identified
(second rising slope before
expiration of td td)
Sends no Tg 7, Tg 8, Tg 9.
Also no status transition to first pulse.
Disabled
LongDoubleClick
Enable
Sends Tg 10, if long double-click
identified (second rising slope after
long pulse)
Sends no Tg 10 and no Tg 11.
Also no status transition to Long
Pulse.
Disabled
DualClick Enable
Sends Tg12, Tg13, if both buttons
pressed within tp
Sends no Tg 12, Tg 13. Also no status
transition to DualClick
Disabled
Process value
Parameterization