P1 and P2 Trunk Applications 

NOTE:  For PC applications, do not disable pin 7 

from being earth grounded on the RS-232 
device that is connected to the Trunk 
Interface II. The Trunk Interface II obtains an 
earth ground reference for the shield 
through the computer’s RS-232 port. 

1. 

Attach the PMD trunk wires to the three-position 
trunk connector as indicated on the rear panel 
of the Trunk Interface II. The shield should be 
taped back or connected as required to obtain a 
single-ended earth grounded shield. 

2. 

Connect the stripped end of the earth ground 
wire to the shield position of the PMD Trunk 
Connector and connect the other end (ring 
terminal) to earth ground (for example, 
mounting plate screw of outlet, field panel 
chassis mounting screw, or other suitable earth 
ground location). 

3. 

Connect the RS-232 cable between the Trunk 
Interface II and the computer’s RS-232 port. 

4. 

Plug the DC power cord into the transformer 
connector on the Trunk Interface II, then plug 
the power pack into the appropriate power 
source (Figure 3). 

Installation is now complete.

 

Figure 2.  Trunk Interface II

 

Jumper Locations. 

 

Figure 3.  Rear Panel of Trunk Interface II. 

 